Owner`s manual
Thermostatic Radiator Valves
Honeywell Water Product Solutions
66 customer.honeywell.com 63-8702
V2000 Series Standard Capacity Thermostatic Radiator Valve Body
Allow automatic temperature control in two-pipe steam or hot
water systems for free standing radiators, convectors and other
heating units with standard capacity requirements. Provide
comfort and energy savings for conversion of manual control.
• Continually monitors and adjusts room temperature for consistent
comfort and relief from under heating and overheating.
• Adjustable balancing cartridge design made from resilient
material(EPDM), ensures tight shut-off on steam and hot water
systems.
• Nickel plated brass casted body.
• Replaceable cartridge for easy service with service tool.
• Controls include sensor, setpoint dial and valve actuator,
components may be integral or connected by capillary tubes.
• No electrical connection required for non-electric acuators.
• Normally open without control mounted.
• Used with MV100 & T100 actuators
Dimensions Diagram
Capacity: Standard
Materials (Body): Nickel Plated Bronze
Differential Pressure Rating: With T100 or T200: 15 psi
(With T100 or T200: 103 kPa)
With MV100: 36 psi (With MV100: 248 kPa)
For low noise: 3 psi (For low noise: 20 kPa)
Pressure Ratings (Hot Water): 150 psi maximum (1034 kPa)
Pressure Ratings (Steam): 15 psi maximum (103 kPa)
Temperature Rating: 248 F Maximum (120 C Maximum)
Cartridge Change Tool: Yes - Use VA8200A001
A
M12933B
B MAX.
V200LD (Straight Body)
A
M12930B
B MAX.
V2040D (Straight Body)
A
M12931B
C
B MAX.
V2040E (Angle Body)
A
M12932B
C
B MAX.
V2040A (Horizontal Angle Body)