System information

14
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set or Get Zone Level 1 0–100 or
0.00–100.00
SS.ss
1
, SS, MM:SS, or HH:MM:SS
Start Raising 2 None
Start Lowering 3 None
Stop Raising / Lowering 4 None
Start Flash
2
5 SS.ss
1
, SS, MM:SS, or HH:MM:SS
Pulse 6 SS.ss
1
, SS, MM:SS, or HH:MM:SS
Set (#) or Get (?)
3,4
Venetian tilt level only
9 Tilt Level
5
= 0 –100
6
or 0.00–100.00
5,6
Fade
1
in: SS.ss
2
, SS, MM:SS, or HH:MM:SS
Delay
3
in: SS.ss
2
, SS, MM:SS, or HH:MM:SS
Set (#) or Get (?)
4
Venetian lift & tilt level
10 Lift Level
5
= 0 –100 or 0.00 –100.00
5
Tilt Level
5
= 0 –100
f
or 0.00–100.00
5,6
Fade
1
in: SS.ss
2
, SS, MM:SS, or HH:MM:SS
Delay
3
in: SS.ss
2
, SS, MM:SS, or HH:MM:SS
Start raising Venetian tilt
11 None
4
Start lowering Venetian tilt
12 None
4
Stop Venetian tilt
13 None
4
Start raising Venetian lift
14 None
4
Start lowering Venetian lift
15 None
4
Stop Venetian lift
16 None
4
Set DMX color / level settings
7
17 Color / level index: 0 –255 / 0.00 –100.00
8
Motor Jog Raise
7
18 None
9
Motor Jog Lower
7
19 None
9
Motor 4-Stage Jog Raise
7
20 None
9
Motor 4-Stage Jog Lower
7
21 None
9
NOTES
1. Fractions are rounded up to the closest 1/4 second.
2. To stop a dimmer from flashing, send it to a valid level (action 1).
3. The Delay time is optional. When not used, the system will use a zero-second delay. The minimum delay time is
0seconds. The maximum delay time is 4 hours.
4. Not supported in Quantum®.
5. For switched outputs, any non-zero level results in on or closed, 0 results in off or open.
6. 50 for Horizontal Sheer Blinds.
7. Not supported in RadioRA® 2.
8. Supported in Quantum® version 2.2 and higher.
9. Supported in Quantum® version 2.5 and higher.
Lutron® integration protocol
OUTPUT Command Format
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#OUTPUT, 6, Action Number, Parameters
Integrator’s Reference (continued)
OUTPUT: Command Summary
Outputs are dimmers, CCOs, or other devices in a system that have a controllable output. All of
these devices will accept levels from 0% to 100% and 0.00% to 100.00% with a given fade and
delay time. These same commands can be monitored in real-time as they occur in the system.