System information

35
Lutron® integration protocol
RadioRA® 2 (continued)
System Commands (continued)
GROUP Commands
Setup
Wired
RF
Communication
Repeater Status
1
3
4
2
M
Main Repeater
Power
Repeater Link
COM
9 V
1
N / C
MUX
MUX
2
3
4
AddTest
Integrate
Program / Integrate
RS232
Ethernet
USB
GROUP Command-specific fields
Action Numbers:
Action Action Number
Get (?) Occupancy Group State
3
GROUP Command Format
Use “GROUP Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
?GROUP, 6, Action Number
Example GROUP Messages
Operation Command String
Query: ?GROUP, Integration ID, Action Number
What is Occ GROUP 1’s status? ?GROUP,1,3<CR><LF>
Response: ~ GROUP, Integration ID, Action Number, Parameters
Occ group 1 is occupied ~GROUP,1,3,3<CR><LF>
Occ group 1 is unknown ~GROUP,1,3,255<CR><LF>
Occupancy States:
Description Value
Occupied 3
Unoccupied 4
Unknown 255