System information

36
Lutron® integration protocol
MONITORING Command Formats
MONITORING Command-specific fields
Monitoring Type:
Description Monitoring Type
Diagnostic Monitoring 1
Button Monitoring (if enabled, button actions will be reported) 3
LED Monitoring (if enabled, LED states will be reported) 4
Zone Monitoring (if enabled, zone levels will be reported, i.e. dimmer, shade, contact closure
output level)
5
Reply State (if disabled, all messages FROM the integration access point will cease) 11
Prompt State (if disabled, the prompt will not be printed to the terminal) 12
Set or Get State of All Monitoring (except Reply and Prompt) 255
Action Numbers:
Action Action Number
Enable 1
Disable 2
Example MONITORING Commands
Operation Command String
Execute: #MONITORING, Monitoring Type, Action Number
Disable Diagnostic Monitoring. #MONITORING,1,2<CR><LF>
Enable Event Monitoring. #MONITORING,2,1<CR><LF>
Query: ?MONITORING, Monitoring Type
Is Diagnostic Monitoring disabled? ?MONITORING,1<CR><LF>
Response: ~MONITORING, Monitoring Type, Action Number
Diagnostic Monitoring is disabled. ~MONITORING,1,2<CR><LF>
Setup
Wired
RF
Communication
Repeater Status
1
3
4
2
M
Main Repeater
Power
Repeater Link
COM
9 V
1
N / C
MUX
MUX
2
3
4
AddTest
Integrate
Program / Integrate
RS232
Ethernet
USB
RadioRA® 2 (continued)
System Commands (continued)
MONITORING Commands
Use “MONITORING Command-specific fields”
tables to complete these command fields.
Operation
Command
#MONITORING, Monitoring Type, Action Number