Lutron ® integration protocol revision N 9 August 2013
Lutron integration protocol ® Revision Update — N NOTE: New to this release The following updates have been made to the LutronR Integration Protocol • Integrator's Reference – DEVICE Command. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9, 10 – OUTPUT Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lutron integration protocol ® Table of Contents HomeWorks® QS About Integration Integration Operations 5 System Overview 56 Operation Characters 5 Integration Access Points 58 Command Types 5 System Commands 60 Command Structure 5 Command Termination 5 Command Examples 6 Integration Access Points 7 Command Rules and Formatting 7 Integrator’s Reference Devices GRAFIK Eye® QS 70 Energi Savr NodeTM QS / DALI® 74 Energi Savr NodeTM QS / EcoSystem® 77 Energi Savr NodeTM QS / Int’l
Lutron integration protocol ® Integration Operations The LutronR integration protocol will allow third-party equipment, such as touch-screens, universal remote controls and software applications, to control and monitor devices in a LutronR lighting control system.
Lutron integration protocol ® Command Examples 1) This command sets a dimmer (1) level to 75% with a 1 minute and 30 second fade time. #OUTPUT,1,1,75,01:30 Command #OUTPUT 2) Integration ID Command-specific fields Action Number Level Fade Time 1 75 01:30 1 This command presses button number 1 of a keypad (2).
Lutron integration protocol ® Integration Access Points • Integration Access Points communicate with external systems using RS232, Ethernet or both. The LutronR integration protocol will allow third-party equipment, such as touch-screens, keypads and software applications, to control and monitor devices in the LutronR lighting control system through an Integration Access Point. For more information, check the page specific to the Integration Access Point being used.
Lutron integration protocol ® Integrator's Reference Compatibility Matrix Integration Access Point Compatibility Matrix: ConnectR QS Standalone QuantumR RadioRAR 2 HomeWorksR QS Clear Gateway System QS Network Interface RadioRAR 2 Main Repeater HomeWorksR QS Processor Clear ConnectR Gateway Device Compatibility Matrix: ConnectR QS Standalone QuantumR RadioRAR 2 HomeWorksR QS Clear Gateway System GRAFIK EyeR QS seeTouchR Keypads Tabletop seeTouchR Keypad
Lutron integration protocol ® Integrator's Reference (continued) DEVICE: Command Summary Device integration commands allow the user to access components of the system such as a physical device. The user can activate programming via button presses, releases, etc., as well as monitor those same events as they occur in real time in the system.
Lutron integration protocol ® Integrator's Reference (continued) DEVICE: Command Summary (continued) DEVICE Command-specific fields (continued) Action Numbers and Parameters: Action Parameters Set or Get Zone Lock 1,2 15 0 = Off 1 = On Set or Get Scene Lock 1,2 16 0 = Off 1 = On Set or Get Sequence State 1,2 17 0 = Off, 1 = Scenes 1–4 2 = Scenes 5–16 Start Raising 3,4 18 None Start Lowering 3,4 19 None 20 None Get battery status 22 1 = Normal, 2 = Low Set a custom lift and tilt level
Lutron integration protocol ® Integrator's Reference (continued) DEVICE: Command Summary (continued) HomeWorks® QS Button Types and Integration Requirements: Refer to LutronR Designer software for setting up programming options.
Lutron integration protocol ® Integrator's Reference (continued) OUTPUT: Command Summary Outputs are dimmers, CCOs, or other devices in a system that have a controllable output. All of these devices will accept levels from 0% to 100% and 0.00% to 100.00% with a given fade and delay time. These same commands can be monitored in real-time as they occur in the system.
Lutron integration protocol ® Integrator's Reference (continued) OUTPUT: Command Summary (continued) OUTPUT Command-specific fields (continued) Action Numbers and Parameters: Action Action Number Parameters Motor Jog Raise 5 18 None 7 Motor Jog Lower 5 19 None 7 Motor 4-Stage Jog Raise 5 20 None 7 Motor 4-Stage Jog Lower 5 21 None 7 NOTES 1. For switched outputs, any non-zero level results in on or closed, 0 results in off or open. 2. Fractions are rounded up to the closest ¼ second. 3.
Lutron integration protocol ® Integrator's Reference (continued) GROUP: Command Summary The GROUP command is used to report the status of a group of occupancy sensors. GROUP Command Format Operation Integration ID (example) ?GROUP, 6, Action Number Use “GROUP Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® Integrator's Reference (continued) MONITORING: Command Summary Monitoring allows the user to configure what types of messages the system will report. Note to Integrator: The default values of these are set in the programming database and restored whenever the integration port is logged in. The user can temporarily change those settings to hide or show information as desired.
Lutron integration protocol ® Integrator's Reference (continued) ERROR: Command Summary Integration Access Points will respond with an error if an invalid command is received. See the table below for explanations of different errors.
Lutron integration protocol ® Integrator's Reference (continued) HELP: Command Summary HELP Command for a specific Command Name provides command-name specific usage information.
Lutron integration protocol ® Integrator's Reference (continued) SYSTEM: Command Summary SYSTEM Command provides support for location, device and system specific information such as Date, Time, Software Version Numbers, etc. SYSTEM Command Formats Operation #SYSTEM, Action Number, Parameters Command Use “SYSTEM Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® QS Standalone — System Overview The QS family of products delivers scalable lighting and shading solutions for residential and commercial applications. At the center of the QS system are the GRAFIK Eye® QS control units, Energi Savr NodeTM control units, and Sivoia® QS shades and drapes, providing direct control of electric and natural light. QS system devices communicate over the highly flexible QS link – the link allows for daisy-chain or t-tap wiring configurations.
Lutron integration protocol ® QS Standalone Integration Access Points Network Interface Model: QSE-CI-NWK-E Why Integrate with a QSE-CI-NWK-E? • Integrates a QS lighting control system with a PC or other digital equipment that supports RS232 or Ethernet TCP/IP connection. • Allows monitor and control of system devices. For example, the QSE-CI-NWK-E can be used to simulate button presses, report button presses, control light levels, and monitor light levels.
Lutron integration protocol ® QS Standalone Integration Access Points (continued) Connection Information Provides an RS232 and Ethernet connection to communicate with external equipment. Communication is through either RS232 or Ethernet, but not both simultaneously.
Lutron integration protocol ® QS Standalone System Commands QSE-CI-NWK-E: ETHERNET Commands ETHERNET Command Formats Operation #ETHERNET, Configuration Number, Parameters Command Use “ETHERNET Command-specific fields” tables to complete these command fields. ETHERNET Command-specific fields Configuration Numbers: Description Configuration Number Parameters Set IP Address 0 Address (XXX.XXX.XXX.XXX) Set Gateway Address 1 Address (XXX.XXX.XXX.XXX) Set Subnet Mask 2 Address (XXX.XXX.XXX.
Lutron integration protocol ® QS Standalone System Commands (continued) QSE-CI-NWK-E: INTEGRATION ID Commands INTEGRATION ID Command Formats Operation #INTEGRATIONID, Action Number, Parameters Command Use “INTEGRATIONID Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® QS Standalone System Commands (continued) QSE-CI-NWK-E: DETAILS String DETAILS Command Formats Operation ?DETAILS, ID 1 Command Example DETAILS String Operation Command String Query: ?DETAILS, ID Get details of the device with serial ID number 00AC123D ?DETAILS,00AC123D Response: ~DETAILS, Serial Number, Name, Family, Model, Software Rev., Boot Software Rev.
Lutron integration protocol ® QS Standalone System Commands (continued) QSE-CI-NWK-E: RESET Commands RESET Command Formats Operation #RESET, Action Number Command Use “RESET Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® QS Standalone System Commands (continued) QSE-CI-NWK-E: PROGRAMMING Commands PROGRAMMING Command Formats Operation Integration ID or Serial # of the QSE-CI-NWK being used #PROGRAMMING, 1, Button Number, Action Number, Parameters Phantom Button Use “PROGRAMMING Command-specific Number (can be 1–100) fields” tables to complete these command fields.
Lutron integration protocol ® QS Standalone System Commands (continued) QSE-CI-NWK-E: PROGRAMMING Commands (continued) Example PROGRAMMING Commands For a system of one shade (Integration ID “living room sheer”), one Venetian blind (“kitchen venetian”), and one QSE-CI-NWK (Integration ID “1”), the following examples show how programming can be done.
Lutron integration protocol ® QS Standalone System Commands (continued) QSE-CI-NWK-E: PROGRAMMING Commands PROGRAMING Command Formats Operation Integration ID or Serial # of the QSE-CI-NWK being used ?PROGRAMMING, 1, Button Number, Action Number Command Phantom Button # (can be 1–100) Use “PROGRAMMING Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® QS Standalone System Commands (continued) QSE-CI-NWK-E: DEVICE Commands DEVICE Command Formats Operation Integration ID or Serial # of the QSE-CI-NWK being used #DEVICE, 1, Button Number, Action Number, Parameters Command Phantom Button Number (can be 1-100) Use “DEVICE Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® RadioRA® 2 - System Overview RadioRAR 2 is a wireless multi-room control system for lights and shades. The system is made up of repeaters, dimmers, keypads, and other devices. The LutronR proven, patented RF technology ensures reliable performance. With the RadioRAR 2 system, you can: create the right ambience for varied activities, easily monitor and control your lights, reduce energy usage, and increase safety in and around your home.
Lutron integration protocol ® RadioRA 2 Integration Access Points Main Repeater ® Model: RR-MAIN-REP-WH, RRK-MAIN-REP-WH USB Main Repeater Repeater Status 1 M 2 3 4 Communication RF Setup Wired Test Power Repeater Link COM N/C MUX MUX 9V 1 2 3 4 Add Integrate RS232 Program / Integrate Ethernet Why Integrate with a RadioRA® 2 Main Repeater? • Integrates a RadioRA® 2 lighting control system with a PC or other digital equipment that supports RS232 or Ethernet TCP/IP communication.
Lutron integration protocol ® USB Main Repeater Repeater Status 1 M 2 3 4 Communication RF Setup Power Repeater Link COM MUX MUX 9V N/C RadioRA® 2 Integration Access Points (continued) Wired Test 1 2 3 4 Add Integrate RS232 Program / Integrate Ethernet Connection Information Provides an RS232 and Ethernet connection to communicate with external equipment.
Lutron integration protocol USB ® Main Repeater Repeater Status 1 M 2 3 4 Communication RF Setup Power Repeater Link COM MUX MUX 9V N/C RadioRA® 2 System Commands RR-MAIN-REP-WH: DEVICE Commands Wired Test 1 2 3 4 Add Integrate RS232 Program / Integrate Ethernet DEVICE Command Formats Operation Integration ID (example) #DEVICE, 1, Component Number, Action Number, Parameters Command Use “DEVICE Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® USB Main Repeater Repeater Status 1 M 2 3 4 Communication RF Setup ?GROUP, 6, Action Number Use “GROUP Command-specific fields” tables to complete these command fields.
Lutron integration protocol USB ® Main Repeater Repeater Status 1 M 2 3 4 Communication RF Setup RadioRA® 2 System Commands (continued) RR-MAIN-REP-WH: MONITORING Commands Wired Test Power Repeater Link COM N/C MUX MUX 9V 1 2 3 4 Add Integrate RS232 Program / Integrate Ethernet MONITORING Command Formats Operation #MONITORING, Monitoring Type, Action Number Command Use “MONITORING Command-specific fields” tables to complete these command fields.
Lutron integration protocol USB ® Main Repeater Repeater Status 1 M 2 3 4 Communication RF Setup Power Repeater Link COM MUX MUX 9V N/C RadioRA® 2 System Commands (continued) RR-MAIN-REP-WH: TIMECLOCK Commands Wired Test 1 2 3 4 Add Integrate RS232 Program / Integrate Ethernet TIMECLOCK Command Formats Operation Integration ID (example) #TIMECLOCK,4,Action Number, Parameters Command Use “TIMECLOCK Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® Clear Connect® Gateway System - System Overview The Clear ConnectR Gateway System is a wireless multi-room control system for lights and shades. The system is made up of repeaters, dimmers, keypads, and other devices. The LutronR proven, patented RF technology ensures reliable performance.
Lutron integration protocol ® Clear Connect Gateway System Integration Access Points ® Models: NXB-CCG, NXB-CCG-K Why Integrate with a Clear ConnectR Gateway System? • Integrates a Clear ConnectR lighting control system with a PC or other digital equipment that supports Ethernet TCP/IP communication. • Allows monitoring and control of system devices. For example, the Translator can be used to simulate button presses, report button presses, monitor LEDs, and control light levels of dimmers.
Lutron integration protocol ® Clear Connect Gateway System Integration Access Points (continued) ® Connection Information Provides an Ethernet connection to communicate with external equipment. Ethernet Configuring the control interface to communicate over a network takes not only knowledge of the Clear ConnectR Gateway System, but of networking as well.
Lutron integration protocol ® Clear Connect Gateway System Integration Access Points (continued) ® Connection Information (continued) System Configuration • Default web admin information NXB-CCG / NXB-CCG-K: - Login: admin - Password: 1988 • XML file extraction is supported a) Browsing to “/xml” after logging in will return the XML data for the system b) Browsing to “/xml?login=&password=” will return the XML data without first having to log in Notes: - The "login" info can use either
Lutron integration protocol ® Clear Connect Gateway System Commands Access Points: DEVICE Commands ® DEVICE Command Formats Operation Integration ID (example) #DEVICE, 1, Component Number, Action Number, Parameters Command Use “DEVICE Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® Clear Connect Gateway System Commands ® (continued) Access Points: Group Commands GROUP Command Format Operation Integration ID (example) ?GROUP, 6, Action Number Use “GROUP Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® Clear Connect Gateway System Commands ® (continued) Access Points: PING Command PING Command Formats Operation #PING Command Example PING Command Operation Command String Execute: #PING Ping to verify connectivity #PING Response: ~PING Connection is established ~PING 43
Lutron integration protocol ® Quantum® - System Overview The QuantumR system is the LutronR premier commercial lighting control system. It allows the control and monitoring of individual devices and outputs as well as allowing control of entire areas, shade groups or other portions of the system. The QuantumR system includes QS devices such as the GRAFIK EyeR QS and SivoiaR QS shades as well as LutronR EcoSystemR ballasts and GRAFIKT dimming panels.
Lutron integration protocol ® Quantum Integration Access Points Network Interface ® Model: QSE-CI-NWK-E Why Integrate with a QSE-CI-NWK-E? • Integrates a QS lighting control system with a PC or other digital equipment that supports RS232 or Ethernet TCP/IP connection. • Allows monitor and control of system devices. For example, the QSE-CI-NWK-E can be used to simulate button presses, report button presses, monitor LEDs, and control light levels.
Lutron integration protocol ® Quantum® Integration Access Points (continued) Connection Information Provides an RS232 and Ethernet connection to communicate with external equipment.
Lutron integration protocol ® Quantum® System Commands QSE-CI-NWK-E: ETHERNET Commands ETHERNET Command Formats Operation #ETHERNET, Configuration Number, Parameters Command Use “ETHERNET Command-specific fields” tables to complete these command fields. ETHERNET Command-specific fields Configuration Numbers: Description Configuration Number Parameters Set IP Address 0 IP Address (XXX.XXX.XXX.XXX) Set Gateway Address 1 IP Address (XXX.XXX.XXX.XXX) Set Subnet Mask 2 IP Address (XXX.XXX.XXX.
Lutron integration protocol ® Quantum® System Commands (continued) QSE-CI-NWK-E: INTEGRATION ID Commands INTEGRATION ID Command Formats Operation ?INTEGRATIONID, Action Number, Parameters Command Use “INTEGRATIONID Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® Quantum® System Commands (continued) QSE-CI-NWK-E: RESET Commands RESET Command Formats Operation #RESET, Action Number Command Use “RESET Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® Quantum® System Commands (continued) QSE-CI-NWK-E: AREA Commands AREA Command Formats Operation Integration ID (example) #AREA 1, 2, 2, Action Number, Parameters Command Use “AREA Command-specific fields” tables to complete these command fields. AREA Command-specific fields Action Numbers and Parameters: Action Action Number Parameters Set (#) Area Level 1 Level 3 = 0–100 or 0.00–100.00 Fade 4 in: SS.ss 5, SS, MM:SS, or HH:MM:SS Delay 4 in: SS.
Lutron integration protocol ® Quantum® System Commands (continued) QSE-CI-NWK-E: AREA Commands (continued) NOTES 1. AREA can only be used to control areas of a QuantumR system that have been assigned to a particular integration access point. Please refer to the Q-DesignT software (Integration Tab) or QuantumR Integration Report for details of what areas are available for control and monitoring. 2. AREA commands cannot be sent to areas that contain other areas, such as a floor or an entire building. 3.
Lutron integration protocol ® Quantum® System Commands (continued) QSE-CI-NWK-E: SHADEGRP Commands SHADEGRP Command Formats Integration ID (example) Operation #SHADEGRP 1, 2, Action Number, Parameters Use “SHADEGRP Command-specific fields” tables to complete these command fields. Command SHADEGRP Command-specific fields Action Numbers and Parameters: Action Action Number Set (#) Shade Group Level 1 Parameters Level 2 = 0–100 or 0.00–100.00, Delay 3 in: SS.
Lutron integration protocol ® Quantum® System Commands (continued) QSE-CI-NWK-E: OUTPUT Commands OUTPUT Command Format Operation Integration ID (example) #OUTPUT 1, 2, Action Number, Parameters Command Use “OUTPUT Command-specific fields” tables to complete these command fields. OUTPUT Command-specific fields Action Numbers and Parameters: Action Set (#) or Get (?) Output Level Action Number 1 Parameters Level 2 = 0–100 or 0.00–100.00 Fade 3 in: SS.ss 4, SS, MM:SS, or HH:MM:SS Delay 3 in: SS.
Lutron integration protocol ® Quantum® System Commands (continued) QSE-CI-NWK-E: OUTPUT Commands OUTPUT Command Format Operation Integration ID (example) #OUTPUT 1,2, Action Number, Parameters Command Use “OUTPUT Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® Quantum® System Commands (continued) QSE-CI-NWK-E: SYSVAR Commands 1 SYSVAR Command Formats Operation #SYSVAR,2,Action Number, Parameters Command Use “SYSVAR Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® HomeWorks® QS - System Overview HomeWorksR QS is Lutron's premier total home control system. It allows control and monitoring of lights, shades, HVAC, sensors and appliances. The HomeWorksR QS system includes QS devices, RF devices and power panels that provide solutions for new construction and retrofit projects of any size.
Lutron integration protocol ® HomeWorks® QS - System Overview (continued) Command Types The following is a list of supported command types. Details on certain device specific types (e.g. DEVICE, HVAC) are located in the individual device section of this manual. Operation characters will be followed by command types.
Lutron integration protocol ® HomeWorks QS Integration Access Points HomeWorks QS Processor ® ® Model: HQP6-2 Why Integrate with a HomeWorks® QS Processor? • Integrating with a HomeWorksR QS Processor provides integration over Ethernet without the need for additional equipment or interfaces. • RS-232 integration can also be accomplished using third party Ethernet to RS-232 adapters.
Lutron integration protocol ® HomeWorks® QS Integration Access Points (continued) Connection Information Ethernet Configuring the HomeWorksR QS processor to communicate over a network takes not only knowledge of the HomeWorksR QS system, but of networking as well. Installers with limited networking knowledge are advised to contact a networking professional before attempting to connect a HomeWorksR QS processor through a network.
Lutron integration protocol ® HomeWorks® QS System Commands HQP6-2: OUTPUT Commands OUTPUT Command Format Operation Integration ID (example) #OUTPUT 1, 2, Action Number, Parameters Use “OUTPUT Command-specific fields” tables to complete these command fields. Command OUTPUT Command-specific fields Action Numbers and Parameters: Action Action Number Parameters Set (#) or Get (?) Output Level 1 Level 2 = 0–100 or 0.00–100.00 Fade 3 in: SS.ss 4, SS, MM:SS, or HH:MM:SS Delay 3 in: SS.
Lutron integration protocol ® HomeWorks® QS System Commands (continued) HQP6-2: OUTPUT Commands (continued) Example OUTPUT Messages Operation Command String Execute: #OUTPUT, Integration ID, Action Number, Parameters Set output level to 70% (Fade = 4 sec, Delay = 2 sec) #OUTPUT,2,1,70,4,2 Raise Output #OUTPUT,2,2 Query: ?OUTPUT, Integration ID What is the current output level? ?OUTPUT,2 Response : ~OUTPUT, Integration ID, Action Number, Parameters 3 Output level is set to 4
Lutron integration protocol ® HomeWorks® QS System Commands (continued) HQP6-2: SHADEGRP Commands SHADEGRP Command Formats Integration ID (example) Operation #SHADEGRP 1, 2, Action Number, Parameters Use “SHADEGRP Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® HomeWorks® QS System Commands (continued) HQP6-2: SHADEGRP Commands (continued) Example SHADEGRP Messages Operation Command String Execute: #SHADEGRP, Integration ID, Action Number, Parameters Set shade group to 70% (Delay = 2 sec). #SHADEGRP,2,1,70,2 Lower shade group.
Lutron integration protocol ® HomeWorks® QS System Commands (continued) HQP6-2: TIMECLOCK Commands TIMECLOCK Command Formats Operation #TIMECLOCK,2,Action Number, Parameters Command Use “TIMECLOCK Command-specific fields” tables to complete these command fields. TIMECLOCK Command-specific fields Action Numbers and Parameters: Action Action Number Parameters Get (?) Sunrise Time 2 None Get (?) Sunset Time 3 None Get (?) Day’s Schedule 4 None Execute (#) event 5 Index of the event to test.
Lutron integration protocol ® HomeWorks® QS System Commands (continued) HQP6-2: SYSVAR Commands SYSVAR Command Formats Operation #SYSVAR,2,Action Number, Parameters Command Use “SYSVAR Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® HomeWorks® QS System Commands (continued) HQP6-2: AREA Commands AREA Command Formats Operation Integration ID (example) #AREA 1, 2, Action Number, Parameters Command Use “AREA Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® HomeWorks® QS System Commands (continued) HQP6-2: ETHERNET Commands ETHERNET Command Formats Operation #ETHERNET, Configuration Number, Parameters Command Use “ETHERNET Command-specific fields” tables to complete these command fields. ETHERNET Command-specific fields Configuration Number and Parameters: Description Configuration Number Parameters Get (?) or Set(#) IP Address 0 IP Address (XXX.XXX.XXX.XXX) Get (?) or Set (#) Gateway Address 1 IP Address (XXX.XXX.XXX.
Lutron integration protocol ® HomeWorks® QS System Commands (continued) HQP6-2: INTEGRATION ID Commands INTEGRATION ID Command Formats Operation #INTEGRATIONID, Action Number, Parameters Command Use “INTEGRATIONID Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® HomeWorks® QS System Commands (continued) HQP6-2: RESET Commands RESET Command Formats Operation #RESET, Action Number Command Use “RESET Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® GRAFIK Eye QS Main Unit ® Models: QSGR-, QSG RJ-, QSGRK-, QSGRM-, QSGRN-, QSGRQ- 1 2 3 4 5 6 Scene 1 Fade Time 03 Seconds OK Why Integrate with a GRAFIK Eye® QS? • Control individual lights and scenes • Query current scene and light levels • Control LEDs of unprogrammed buttons Integration Capabilities • 16 scenes and up to 24 controllable outputs (output count depends on model) Supported Command Types • DEVICE allows control and monitoring of buttons, LEDs
Lutron integration protocol ® 1 2 3 4 5 6 Scene 1 Fade Time 03 Seconds OK GRAFIK Eye® QS: DEVICE Commands DEVICE Command Formats Operation Integration ID (example) #DEVICE, 5, Component Number, Action Number, Parameters Command Use “DEVICE Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® 1 2 3 4 5 6 Scene 1 Fade Time 03 Seconds OK GRAFIK Eye® QS: DEVICE Commands (continued) DEVICE Command-specific fields (continued) Component Numbers: Component Component Number Available Actions Shade Column 1 Open LED 174 Get (?) LED state Shade Column 1 Preset 1 LED 175 Get (?) LED state Shade Column 1 Close LED 211 Get (?) LED state Shade Column 2 Open LED 183 Get (?) LED state Shade Column 2 Preset 1 LED 184 Get (?) LED state Shade Column 2 Close L
Lutron integration protocol ® 1 2 3 4 5 6 Scene 1 Fade Time 03 Seconds OK GRAFIK Eye® QS: OUTPUT Commands OUTPUT Command Format Operation Integration ID (example) #OUTPUT, 1, Action Number, Parameters Command Use “OUTPUT Command-specific fields” tables to complete these command fields. OUTPUT Command-specific fields Action Numbers and Parameters: Action Action Number Set or Get Zone Level 1 Parameters Level = 0–100 or 0.00–100.00 Fade 2 in: SS.ss 1, SS, MM:SS, or HH:MM:SS Delay 2, 3 in: SS.
Lutron integration protocol ® Energi Savr Node™ QS for DALI ® QS Model: QSNE-2DAL-D HomeWorksR QS Model: LQSNE-2DAL-D COM 24 V MUX MUX Occ Test N ® QSNE-2DAL-D Z096 N1771 230 V~ 50/60 Hz 100 mA www.lutron.com +44.(0)20.7680.
N 24 V MUX MUX QSNE-2DAL-D Test 230 V~ 50/60 Hz 100 mA www.lutron.com +44.(0)20.7680.
N 24 V MUX MUX QSNE-2DAL-D Test 230 V~ 50/60 Hz 100 mA www.lutron.com +44.(0)20.7680.
Lutron integration protocol ® Energi Savr Node™ QS with EcoSystem ® Model: QSN-2ECO-S Energi Savr Node™ QS with International EcoSystem ® QS Model: QSNE-2ECO-D HomeWorksR QS Model: LQSE-2ECO-D QSNE-2ECO-D QSN-2ECO-S Why Integrate with an Energi Savr NodeTM? • Control individual zones and scenes in an area • Query current scene and light levels Integration Capabilities • Up to 100 areas with 16 scenes per area.
Lutron integration protocol ® Energi Savr Node™ QS with EcoSystem® / International: DEVICE Commands 5 DEVICE Command Formats Operation Integration ID (example) #DEVICE, 5, Component Number, Action Number, Parameters Command Use “DEVICE Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® Energi Savr Node™ QS with EcoSystem® / International: OUTPUT Commands OUTPUT Command Format Operation Integration ID (example) #OUTPUT, 1, Action Number, Parameters Command Use “OUTPUT Command-specific fields” tables to complete these command fields. OUTPUT Command-specific fields Action Numbers and Parameters: Action Action Number Set or Get Zone Level 1 Parameters Level = 0–100 or 0.00–100.00, Fade 2 in: SS.ss 1, SS, MM:SS, or HH:MM:SS Delay 2, 3 in: SS.
Lutron integration protocol ® Energi Savr Node™ QS for International 0-10V / Switching QS Models (QSNE-): 4T10-D, 4S10-D HomeWorksR QS Models (LQSE-): 4T10-D, 4S10-D Energi Savr Node™ QS International Phase Adaptive QS Model: QSNE-4A-D HomeWorksR QS Model: LQSE-4A-D Energi Savr Node™ QS for 0-10V / Switching Models (QSN-): 4T16-S, 4S16-S QSNE-4T10-D QSN-4T16-S QSNE-4A-D 800 W Max 500 W Max 500 W Max 500 W Max Input S1 S2 S3 S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 Type Input Hi Temp Prog Power QSNE
Lutron integration protocol ® 800 W Max 500 W Max 500 W Max 500 W Max Input S1 S2 S3 S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 Type Prog Power 230 V~ 50 / 60 Hz 10 A QSNE-4A-D Photo Occ Switch Hi Temp DIN Rail Power Module IR Input Option Def H Opt1 M Opt2 L Opt3 www.lutron.com +44.(0)20.7702.
Lutron integration protocol ® 800 W Max 500 W Max 500 W Max 500 W Max Input S1 S2 S3 S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 Type Prog Power 230 V~ 50 / 60 Hz 10 A QSNE-4A-D Photo Occ Switch Hi Temp DIN Rail Power Module IR Input Option Def H Opt1 M Opt2 L Opt3 www.lutron.com +44.(0)20.7702.
Lutron integration protocol ® 800 W Max 500 W Max 500 W Max 500 W Max Input S1 S2 S3 S4 CCI Zone 1 Zone 2 Zone 3 Zone 4 Type Prog Power 230 V~ 50 / 60 Hz 10 A QSNE-4A-D Photo Occ Switch Hi Temp DIN Rail Power Module IR Input Option Def H Opt1 M Opt2 L Opt3 www.lutron.com +44.(0)20.7702.
Lutron integration protocol ® Energi Savr Node™ QS for International Motor Module QS Model: QSE-CI-4M-D HomeWorksR QS Model: LQSE-4M-D LQSE-4M-D Why Integrate with an Energi Savr NodeTM? • Control individual zones and scenes in an area • Query current scene and motor levels Integration Capabilities • Up to 4 zones Supported Command Types • DEVICE allows control and monitoring of zone levels and area scenes • OUTPUT allows control and monitoring of the dimmer device output Compatibility Conne
Lutron integration protocol ® Energi Savr Node™ QS for International Motor Module: OUTPUT Commands OUTPUT Command Format Operation Integration ID (example) #OUTPUT, 3, Action Number, Parameters Command Use “OUTPUT Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® Remote Power Modules Adaptive Phase Control Models: HW-RPM-4A, Phase Control Models: HW-RPM-4U Quiet Fan Speed Control Models: H W-RPM-4FSQ 3-Wire Motor Control: HW-RPM-4M Relay Switching: HW-RPM-4R HW-RPM-4A Why Integrate with a Remote Power Module? • Control individual zones and scenes in an area • Query current scene and light levels Integration Capabilities • Up to four zones on each remote power module Supported Command Types • OUTPUT allows control and mon
Lutron integration protocol ® Remote Power Module: OUTPUT Commands OUTPUT Command Format Operation Integration ID (example) #OUTPUT, 6, Action Number, Parameters Command Use “OUTPUT Command-specific fields” tables to complete these command fields. OUTPUT Command-specific fields Action Numbers and Parameters: Action Action Number Set or Get Zone Level 1 Parameters 0–100 or 0.00–100.00 SS.
Lutron integration protocol ® Architrave™ Keypads QS Models (QSWAS-) with Faceplate / Button Kit Models (KP5-, KP7-): DN, KP7 HomeWorksR QS Models (HQWA-) with Faceplate / Button Kit Models (KP5-, KP7-): DN, KP7 KP5-DN KP7-DN QS HomeWorksR QS Button 1 Button 2 Button 3 Button 4 Button 5 Raise Lower Button 1 Button 2 Button 3 Button 4 Button 5 Button 6 Button 7 QS HomeWorksR QS Button 1 Button 2 Button 3 Button 4 Button 5 Button 6 Button 7 Button 1 Button 2 Button 3 Button 4 Button 5 Button 6 Bu
Lutron integration protocol ® Architrave™ Keypads: DEVICE Commands DEVICE Command Formats Operation Integration ID (example) #DEVICE, 2, Component Number, Action Number, Parameters Command Use “DEVICE Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® Architrave™ Keypads: DEVICE Commands (continued) DEVICE Command-specific fields (continued) Action Numbers and Parameters: Action Action Number Parameters Press 3 None Release 4 None Hold 5 None 1 Multi-tap 6 None 1 Set (#) or Get (?) LED State 2 9 0 = Off 1 = On 2 = Normal-Flash: 1 flash every second 1 3 = Rapid-Flash: 10 flashes every second 1 Hold Release 32 None 1 Example DEVICE Commands Examples presume keypad has been assigned Integration ID 2.
Lutron integration protocol ® Signature Series™ Keypads QS Models (QSWAS-): 1 B, 1RLD, 2B, 2BRL, 2RLD, 3B, 3BD, 3BRL, 5B, 5BRL, 7B HomeWorksR QS Models (HQWAS-B, HQWAS-G) with Faceplate / Button Kit Models (LFS-W): 1B, 1RLD, 2BS, 2RLD, 3BS, 3BD, 3BSRL, 4BS, 4S, 5B, 5BRL, 6B, 6BRL, 7B 1B 1RLD 1 2 3 2BS 2BRL 2B 4 5 3BRL 1 2 3 2 3 4 5 6 7 5BRL 5BT 1 2 3 4 5 1 2 3 4 5 4BS 3BSRL 2 3 4 2 3 5 6 3BD 3BS 1 2 3 4 3 4 4 3B 2RLD 5 6 4S 1 1 3 3 5 5 6 5B 1 2 3 4 2 3 4 5 6 6 7
Lutron integration protocol ® Signature Series™ Keypads: DEVICE Commands DEVICE Command Formats Operation Integration ID (example) #DEVICE, 2, Component Number, Action Number, Parameters Command Use “DEVICE Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® Signature Series™ Keypads: DEVICE Commands (continued) DEVICE Command-specific fields (continued) Action Numbers and Parameters: Action Action Number Parameters Press 3 None Release 4 None Hold 5 None 1 Multi-tap 6 None 1 Set (#) or Get (?) LED State 2 9 0 = Off 1 = On 2 = Normal-Flash: 1 flash every second 1 3 = Rapid-Flash: 10 flashes every second 1 Hold Release 32 None Example DEVICE Commands Examples presume keypad has been assigned Integration ID 2.
Lutron integration protocol ® seeTouch Keypads ® QS Models (QSWS2-): 1 B, 1RLD, 2B, 2BRL, 2BRLIR, 2RLD, 3B, 3BD, 3BRL, 3BRLIR, 5B, 5BRL, 5BRLIR, 7B RadioRAR 2 Models (RRD-W): 1 RLD, 2RLD, 3BD, 3BRL, 3BSRL, 4S, 5BRL, 5BRLIR, 6BRL, 7B HomeWorksR QS Models (HQRD-W, HQWD-W, HQWA-W, HQRA-W, HQWAS-W): 1B, 1RLD, 2BS, 2RLD, 3BS, 3BD, 3BSRL, 4BS, 4S, 5B, 5BRL, 5BIR, 6B, 6BRL, 7B Clear ConnectR Device Models (CCD-W): 6BRL 1B 1RLD 2BS 2BRLIR 2BRL 2B 2RLD Button 1 Button 1 Button 2 Button 2 Button 3 But
Lutron integration protocol ® seeTouch® Keypads: DEVICE Commands DEVICE Command Formats Operation Integration ID (example) #DEVICE, 2, Component Number, Action Number, Parameters Command Use “DEVICE Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® seeTouch® Keypads: DEVICE Commands (continued) DEVICE Command-specific fields (continued) Action Numbers and Parameters: Action Action Number Parameters Press 3 None Release 4 None Hold 5 None 1 Multi-tap 6 None 1 Set (#) or Get (?) LED State 2 9 0 = Off 1 = On 2 = Normal-Flash: 1 flash every second 1 3 = Rapid-Flash: 10 flashes every second 1 Example DEVICE Commands Examples presume keypad has been assigned Integration ID 2.
Lutron integration protocol ® seeTouch QS International Keypads ® QS Models (QSWE-): 2B, 3B, 4B, 5BRL, 5BRLIR, 6BRL, 7BRL, 8BRL, 8BRLIR, 10BRL HomeWorksR QS Models (HWQIS-NB-NONE) with Faceplate / Button Kit Models (LFS-W): 2B, 3B, 4B, 5BRL, 5BRLIR, 6BRL, 7BRL, 8BRL, 8BRLIR, 10BRL 2B 4B 3B 5BRL Button 6 Button 6 Button 7 Button 2 Button 7 Button 4 Button 9 Button 7 Button 8 Button 8 Button 9 Button 9 Button 10 Button 10 Lower Raise 5BRLIR 7BRL 6BRL Button 6 Button 1 Button 6 Bu
Lutron integration protocol ® seeTouch® QS International Keypads: DEVICE Commands DEVICE Command Formats Operation Integration ID (example) #DEVICE, 2, Component Number, Action Number, Parameters Command Use “DEVICE Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® seeTouch® QS International Keypads: DEVICE Commands (continued) DEVICE Command-specific fields (continued) Action Numbers and Parameters: Action Action Number Parameters Press 3 None Release 4 None Hold 5 None 6 None 9 0 = Off Multi-tap Set (#) or Get (?) LED State 1 1 = On 2 = Normal-Flash: 1 flash every sec 3 = Rapid-Flash: 10 flashes every sec Hold Release 32 None Example DEVICE Commands Examples presume keypad has been assigned Integration ID 2.
Lutron integration protocol ® Tabletop seeTouch Keypads ® RadioRAR 2 Models (RR-): T 5RL, T10RL, T15RL HomeWorksR QS Models (HQR-, HQK-, HQQ-, HQM-, HQN-): T5RL, T10RL, T15RL, T5CRL, T10CRL, T15CRL T5-RL T10-RL Button 17 All On Button 1 Button 6 Button 1 Button 2 Button 7 Button 2 Button 3 Button 8 Button 3 Button 4 Button 9 Button 4 Button 5 Button 10 Button 5 Button 16 Button 17 Button 16 All Off Column 3: Lower Column 3: Raise All On All Off Column 3: Lower Column 3: Raise T
Lutron integration protocol ® Tabletop seeTouch® Keypads: DEVICE Commands DEVICE Command Formats Operation Integration ID (example) #DEVICE, 3, Component Number, Action Number, Parameters Command Use “DEVICE Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® Tabletop seeTouch® Keypads: DEVICE Commands (continued) DEVICE Command-specific fields (continued) Component Numbers: Component Component Number Available Actions LED 1 81 Set or Get LED state LED 2 82 Set or Get LED state LED 3 83 Set or Get LED state LED 4 84 Set or Get LED state LED 5 85 Set or Get LED state LED 6 86 Set or Get LED state LED 7 87 Set or Get LED state LED 8 88 Set or Get LED state LED 9 89 Set or Get LED state LED 10 90 Set or
Lutron integration protocol ® Hybrid Keypad RadioRAR 2 Models (RRD-H): 1RLD, 2RLD, 3BSRL, 4S, 5BRL, 6BRL HomeWorksR QS Models (HQRD-H): 1RLD, 2RLD, 3BSRL, 4S, 5BRL, 6BRL H6BRL Why Integrate with a Hybrid Keypad? • Turn On to specific light level or Off • Raise / Lower light level • Query current light level Additional Commands • None Compatibility ConnectR QS Standalone QuantumR RadioRAR 2 HomeWorksR QS Clear Gateway System Hybrid Keypad 103
Lutron integration protocol ® Hybrid Keypad: OUTPUT Commands OUTPUT Command Format Operation Integration ID (example) #OUTPUT, 1, Action Number, Parameters Command Use “OUTPUT Command-specific fields” tables to complete these command fields. OUTPUT Command-specific fields Action Numbers and Parameters: Action Action Number Set or Get Zone Level 1 Parameters Level = 0–100 or 0.00–100.00, Fade 2 in: SS.ss 1, SS, MM:SS, or HH:MM:SS Delay 2 in: SS.
Lutron integration protocol ® Hybrid Keypad: DEVICE Commands DEVICE Command Formats Operation Integration ID (example) #DEVICE, 2, Component Number, Action Number, Parameters Command Use “DEVICE Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® Hybrid Keypads: DEVICE Commands (continued) DEVICE Command-specific fields (continued) Action Numbers and Parameters: Action Action Number Parameters Press 3 None Release 4 None Set (#) or Get (?) LED State 9 0 = Off 1 = On 2 = Normal-Flash: 1 flash every second 1 3 = Rapid-Flash: 10 flashes every second 1 NOTE 1. "Set" is for LEDs on unprogrammed buttons and buttons with LED logic 'Defined by Integration.
Lutron integration protocol ® Pico Wireless Controls ® CURRENT MODELS: PJ-2B, PJ-3B, PJ-2BRL, PJ-3BRL LEGACY QS Models (QSR4P-, QSR8P-, QSRKP-, QSRMP-,): 2, 2R, 3R RadioRAR 2 Models (RRD- P): 3BRL-L, 3BRL-S 2B 2BRL Button 1 Button 1 Button Raise Button Lower Button 3 Button 3 3BRL 3B Button 1 Button 1 Button Raise Button 2 Button 2 Button Lower Button 3 Button 3 Why Integrate with a Pico® Wireless Control? • Simulate a button press • Monitor button presses Compatibility ConnectR QS Standa
Lutron integration protocol ® Pico® wireless controls: DEVICE Commands DEVICE Command Formats Operation Integration ID (example) #DEVICE, 2, Component Number, Action Number, Parameters Command Use “DEVICE Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® Dynamic Keypad Model: HQ-J-DK420 HQ-J-DK420 Why Integrate with a Dynamic Keypad? • Recognize a button press / release in order to control a third party device from the Dynamic Keypad’s user interface • Simulate a button press • Control LEDs of unprogrammed buttons Compatibility ConnectR QS Standalone QuantumR RadioRAR 2 HomeWorksR QS Clear Gateway System Dynamic Keypad 109
Lutron integration protocol ® Dynamic Keypad: DEVICE Commands DEVICE Command Formats Operation Integration ID (example) #DEVICE, 2, Component Number, Action Number, Parameters Command Use “DEVICE Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® Wallbox Input Closure Interface Model: QSE-CI-WCI 12345678 ON 1 QSE-CI-WCI 2 ® INPUTS ENTRADA ENTRÉES COM 12345678 Why Integrate with a Wallbox Input Closure? • Simulate a button press Compatibility ConnectR QS Standalone QuantumR RadioRAR 2 HomeWorksR QS Clear Gateway System Wallbox Input Closure Interface 111
Lutron integration protocol 12345678 ® ON 1 QSE-CI-WCI INPUTS ENTRADA ENTRÉES Wallbox Input Closure Interface: DEVICE Commands Integration ID (example) #DEVICE, 2, Component Number, Action Number, Parameters Command Use “DEVICE Command-specific fields” tables to complete these command fields.
Lutron integration protocol 12345678 ® ON 1 QSE-CI-WCI INPUTS ENTRADA ENTRÉES Wallbox Input Closure Interface: DEVICE Commands (continued) 2 ® COM 12345678 DEVICE Command-specific fields (continued) Action Numbers and Parameters: Action Action Number Parameters Press 3 None Release 4 None Hold 5 None 1 Multi-tap 6 None 1 Set (#) or Get (?) LED State 2 9 0 = Off 1 = On 2 = Normal-Flash: 1 flash every second 1 3 = Rapid-Flash: 10 flashes every second 1 Hold Release 32 None 1 Ex
Lutron integration protocol ® Sivoia QS Shades Sivoia QS Wireless Shades ® ® Why Integrate with Sivoia® QS Shades? • Set shades to a specific level • Query current level Integration Capabilities • One controllable output (use OUTPUT command) Supported Command Types • OUTPUT allows control and monitoring of the shade output • SHADEGRP allows control of shade groups in a Quantum® or HomeWorks® QS system. Shade Groups are collections of shades that operate in unison.
Lutron integration protocol ® Sivoia® QS Shades: OUTPUT Commands OUTPUT Command Format Operation Integration ID (example) #OUTPUT, 1, Action Number, Parameters Command Use “OUTPUT Command-specific fields” tables to complete these command fields. OUTPUT Command-specific fields Action Numbers and Parameters: Action Action Number Set (#) or Get (?) Zone Level 1 Parameters Level 2 = 0–100 or 0.00–100.00 1 Fade 3 in: SS.ss 4, SS, MM:SS, or HH:MM:SS Delay 5 in: SS.
Lutron integration protocol ® Sivoia® QS Shades: OUTPUT Commands SHADEGRP Command Formats Integration ID (example) Operation #SHADEGRP 1, 2, Action Number, Parameters Use “SHADEGRP Command-specific fields” tables to complete these command fields. Command SHADEGRP Command-specific fields Action Numbers and Parameters: Action Action Number Parameters Set (#) or Get (?) Shade Group Level 6 1 Level 2 = 0–100 or 0.00–100.
Lutron integration protocol ® Sivoia QS Venetian Blinds Sivoia QS Wireless Venetian Blinds ® ® Why Integrate with Sivoia® QS Venetian Blinds? • Set Venetian blind tilt, lift to specific levels • Query current tilt, lift levels Integration Capabilities • One controllable output (use OUTPUT command) Supported Command Types • OUTPUT allows control and monitoring of the Venetian blind output • SHADEGRP allows control of shade groups in a Quantum® or HomeWorks® QS system.
Lutron integration protocol ® Sivoia® QS Venetian Blinds: OUTPUT Commands OUTPUT Command Format Operation Integration ID (example) #OUTPUT, 1, Action Number, Parameters Command Use “OUTPUT Command-specific fields” tables to complete these command fields. OUTPUT Command-specific fields Action Numbers and Parameters: Action Action Number Set (#) or Get (?) Venetian lift level only 1 Parameters Lift Level 1 = 0–100 or 0.00–100.00 1 Fade 2 in: SS.ss 3, SS, MM:SS, or HH:MM:SS Delay 4 in: SS.
Lutron integration protocol ® NOTES 1. 2. Fade is not available for blinds since they move at a constant rate. The parameter must be entered but is ignored. 3. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a delay time is specified as 1.45 seconds a value of 1.25 seconds will be used. 4. The Delay time is optional. When not used, the system will use a zero second delay. The minimum delay time is 0.25 seconds. The maximum delay time is 4 hours.
Lutron integration protocol ® Maestro Dimmers & Plug-In Modules ® RadioRAR 2 Models (RRD-): 6D, 6NA, 8ANS, 8S-DV, 10D, 10ND, F6AN-DV, 3LD RadioRAR 2 Models (RR-): 3PD, 15APS HomeWorksR QS Models (HQRD-, HQRA): 6D, 6ND, 10D, 10ND, 6NA, F6AN-DV, 8ANS, 8S-DV HomeWorksR QS Models (HWD-, HWA-): 6D, 6ND, 10D, 10ND, 5NE *, 8ANS HomeWorksR QS Models (HQR-): 3PD-1, 15APS-1, 3LD Clear ConnectR Device Models (CCD-W): 6D, 6NA, F6AN-DV, 15APS-1 6D 3PD LUTRON Why Integrate with a MaestroR Dimmer or Plug-In Module?
Lutron integration protocol ® Maestro® Dimmers: OUTPUT Commands LUTRON OUTPUT Command Format Operation Integration ID (example) #OUTPUT, 1, Action Number, Parameters Command Use “OUTPUT Command-specific fields” tables to complete these command fields. OUTPUT Command-specific fields Action Numbers and Parameters: Action Action Number Set or Get Zone Level 1 Parameters Level = 0–100 or 0.00–100.00, Fade 2 in: SS.ss 1, SS, MM:SS, or HH:MM:SS Delay 2 in: SS.
Lutron integration protocol ® Maestro® Dimmers: DEVICE Commands DEVICE Command Format Operation Integration ID (example) #DEVICE 1, 2, Component Number, Action Number, Parameters Command Use “OUTPUT Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® Maestro Fan Speed Control ® RadioRAR 2 Models (RRD-): 2ANF HomeWorksR QS Models (HQRD-, HQRA-, HWD-, HWA-): 2ANF 2ANF LUTRON LUTRON Why Integrate with a MaestroR Dimmer or Plug-In Module? • Turn On to specific speed (High, Medium-High, Medium, Low or Off) • Raise / Lower fan speed • Query current speed Additional Commands • None Compatibility ConnectR QS Standalone QuantumR RadioRAR 2 HomeWorksR QS Clear Gateway System RadioRA® 2 Fan Speed Control HomeWorks® QS Fan
Lutron integration protocol ® Maestro® Fan Speed Control: OUTPUT Commands OUTPUT Command Format Operation Integration ID (example) #OUTPUT 1, 1, Action Number, Parameters Command Use “OUTPUT Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® Visor Control Receiver RadioRAR 2 Model: RR-VCRX HomeWorksR QS Model: HQR-VCRX RR-VCRX Visor Control Receiver Security Input Inputs Full Flash Outputs Keypad Visor Transmitter Learn Power Inputs Outputs 9V 1 Full 2 Flash C 1 C 2 C 3 C 4 C Why Integrate with a Visor Control Receiver? • Simulate a keypad press or contact closure inputs • Control LEDs of unprogrammed buttons • Control contact closure outputs Additional Commands • None Compatibility C
Lutron integration protocol ® Visor Control Receiver Inputs Security Input Outputs Keypad Full Flash Visor Control Receiver: DEVICE Commands Visor Transmitter Learn Power Operation Inputs Outputs 9V DEVICE Command Formats 1 Full 2 Flash C 1 Integration ID (example) #DEVICE, 5, Component Number, Action Number, Parameters Command Use “DEVICE Command-specific fields” tables to complete these command fields.
Lutron integration protocol ® Visor Control Receiver Inputs Security Input Outputs Keypad Full Flash Visor Control Receiver: DEVICE Commands (continued) Visor Transmitter Learn Power Inputs Outputs 9V Example DEVICE Commands 1 Full 2 Flash C 1 C 2 C 3 C 4 C Examples presume Visor Control Receiver has been assigned Integration ID 5. Operation Command String Execute: #DEVICE, Integration ID, Component Number, Action Number, Parameters Press Scene 1.
Lutron integration protocol ® Visor Control Receiver Inputs Security Input Outputs Keypad Full Flash Visor Control Receiver: OUTPUT Commands Visor Transmitter Learn Power Operation Inputs Outputs 9V OUTPUT Command Format 1 Full 2 Flash C 1 C 2 C 3 C 4 C Integration ID (example) #OUTPUT,21, Action Number, Parameters Command Use “OUTPUT Command-specific fields” tables to complete the parameter field.
Lutron integration protocol ® Radio Powr Savr™ Sensors CURRENT Models (LRF2-, CCD-): O CR2B, VCR2B, OKLB, OHLB, OWLB, VKLB, VHLB, VWLB LEGACY Models (LRF2-): OCRB, VCRB LRF2-OCR2B LRF2-OKLB Why Integrate with a Radio Powr SavrTM sensor? • Monitor occupied, unoccupied status of a single sensor Compatibility ConnectR QS Standalone QuantumR RadioRAR 2 HomeWorksR QS Clear Gateway System Radio Powr SavrT Sensors 129
Lutron integration protocol ® Radio Powr Savr™: DEVICE Commands DEVICE Command Formats Operation Integration ID (example) ~DEVICE, 19, 2, Action Number Command Occupied state component is always 2 for sensors DEVICE Command-specific fields Component Numbers: Component Component Number Occupied State 2 Available Actions Occupied, Unoccupied Action Numbers: Action Action Number Occupied 3 Unoccupied 4 Example DEVICE Commands Examples presume sensor has been assigned Integration ID 19.
Lutron integration protocol ® HVAC Controller MODELS (LR-): HVAC-1-WH, HWLV-HVAC LR-HVAC-1-WH LR-HWLV-HVAC Why Integrate with a HVAC Controller? • Get current temperature • Set or get heat setpoints and cool setpoints • Set or get operating mode, fan mode and eco mode • Get connection status to the temp sensor • Get schedule information and hold schedules Supported Command Types • HVAC allows control and monitoring of the HVAC Controller Compatibility ConnectR QS Standalone QuantumR RadioRA
Lutron integration protocol ® HVAC Controller: HVAC Commands HVAC Command Format Operation Integration ID (example) #HVAC,21, Action Number, Parameters Command Action number is always 1 for visor control outputs Use “HVAC Command-specific fields” tables to complete the parameter field.
Lutron integration protocol ® NOTES * Schedule Unavailable –> Schedule not programmed or device needs date / time. Following Schedule –> Running programmed schedule; set points from schedule. Permanent Hold –> Schedule is not running; set points as adjusted. Temporary Hold –> Running schedule; set points as adjusted. Returns to following schedule at next schedule event. ** HomeWorksR QS software version 4.1 and higher.
Lutron integration protocol ® HVAC Controller: HVAC Commands (continued) Example HVAC Commands Operation Command String Execute: #HVAC, Integration ID, Action Number, Parameters Set Heat Setpoint to 68 °F and Cool Setpoint to 72 °F. #HVAC,1,2,68,72 Set System Mode to Cool. #HVAC,1,3,3 Turn Eco Mode On.
Lutron integration protocol ® Wireless Temperature Sensor Model: LRF2-TWRB LRF2-TWRB Link Test Why Integrate with a Wireless Temperature Sensor? • Get battery status Note: To get current temperature, see HVAC Controller on page 132.
Lutron integration protocol ® Link Wireless Temperature Sensor: DEVICE Commands DEVICE Command Formats Operation Integration ID (example) ?DEVICE, 1, Component Number, Action Number, Parameters Command Use “DEVICE Command-specific fields” tables to complete these command fields.
Worldwide Technical and Sales Assistance If you have questions concerning the installation or operation of this product, call Lutron® Technical Support Center. Please provide the exact model number when calling. Model number can be found on the product packaging. Example: SZ-CI-PRG U.S.A., Canada, and the Caribbean: 1.800.523.9466 Other countries call: +1.610.282.3800 Fax: +1.610.282.1243 Visit us on the web at www.lutron.