System information

60
Lutron® integration protocol
OUTPUT Command Format
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) or Get (?) Output Level 1 Level
2
= 0 –100 or 0.00 –100.00
Fade
3
in: SS.ss
4
, SS, MM:SS, or HH:MM:SS
Delay
3
in: SS.ss
4
, SS, MM:SS, or HH:MM:SS
Start Raising
5
2 None
Start Lowering
5
3 None
Stop Raising / Lowering
5
4 None
Flash (#) or Get (?) Flash Frequency 5 Fade
3
in: SS.ss
4
, SS, MM:SS, or HH:MM:SS
Delay
3
in: SS.ss
4
, SS, MM:SS, or HH:MM:SS
Set Pulse CCO (#) 6 Pulse
6
time in: SS.ss
4
, SS, MM:SS, or HH:MM:SS,
or Delay
3
in: SS.ss
4
, SS, MM:SS, or HH:MM:SS
Set (#) Venetian Shade Tilt to a
specified level
9 Tilt level in % = 0.00-100
Fade
3
in: SS.ss
4
, SS, MM:SS, or HH:MM:SS
Delay
3
in: SS.ss
4
, SS, MM:SS, or HH:MM:SS
Set (#) Venetian Shade Tilt and Lift to a
specified level
10 Lift
2
= 0 –100 or 0.00 –100.00,
Tilt
2
= 0 –100 or 0.00 –100.00,
Fade
3
in: SS.ss
4
, SS, MM:SS, or HH:MM:SS
Delay
3
in: SS.ss
4
, SS, MM:SS, or HH:MM:SS
Raise (#) Tilt Output Level 11 None
Lower (#) Tilt Output Level 12 None
Stop (#) Raise / Lower Tilt Output Level 13 None
Raise(#) Lift Output Level 14 None
Lower(#) Lift Output Level 15 None
Stop (#) Raise / Lower Lift Output Level 16 None
NOTES
1. OUTPUT commands can be used to control system lighting zones, individual shades, and contact closed outputs.
2. The Level/Lift/Tilt is taken as a percentage.
3. The Fade and Delay time are optional. When not used the system will use a one second fade time with zero second
delay. The minimum fade and delay time is 0 seconds. The maximum fade and delay time is 4 hours. For shade outputs,
the Fade parameter has no effect (since shades have fixed speeds) but it is required when specifying an optional delay.
4. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a fade time is specified
as 1.45 seconds a value of 1.25 seconds will be used.
5. When a Raise / Lower command is issued, the output’s level will continue to go towards high end / low end until a Stop
command is received.
6. The default time is one second.
HomeWorks® QS System Commands
HQP6-2: OUTPUT Commands
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#OUTPUT
1
, 2, Action Number, Parameters