Product Manual

2322
Remote Control Accessory
The remote control panel and 9-pin D-connector are an optional feature for this product line.
The remote control panel allows the unit to be operated remotely and duplicates all the
diagnostic LED indicators with audible alarm. A built-in dimmer switch allows you to control
the brightness of the remote control LEDs.
CAUTION: DO CONNECT THE REMOTE CONTROL TO THE CHARGER WHILE IT IS ON!
To prevent the possibility of high voltage electrical shock, the charger must be OFF when
connecting the remote control panel. Do not remove the protective dust-cover on the remote
control port if it is not being used.
CAUTION: DO NOT CONNECT THIS PORT TO A COMPUTER!
This will cause serious damage to the battery charger and computer. This damage is not be
covered under the warranty.
IMPORTANT: This remote can only be
used on Battery Chargers manufactured
by Analytic Systems.
DRY CONTACT RELAY
The relay is factory preset to fail when the LOW OUTPUT VOLT LED and alarm buzzer come
on. Both normally open and normally closed contacts are available on the connector. If your
system detects an alarm condition when the charger is operating normally, simply move the
wire connected to Pin 1 of the dry contact terminal block to Pin 3, or vice versa as needed
Pin Function
1 Dry Contact Relay (Closed for fault)
6 Dry Contact Relay (Closed for fault)
2 Remote Off (Short to 5 to turn unit OFF)
7 OverTemp (Low for fault)
3 UnderVolt In (Low for fault)
8 OverLoad (Low for fault)
4 UnderVolt Out (Low for fault)
9 +12 Volts
5 Common