INSTALLATION & OPERATION MANUAL IPSi1200-125 HIGH VOLTAGE PURE-SINE INVERTER An ISO9001 Registered Company Battery Chargers • Inverters • Power Supplies • Voltage Converters 8128 River Way, Delta B.C. V4G 1K5 Canada T. 604.946.9981 F. 604.946.9983 TF. 800.668.3884 (US/CANADA) www.analyticsystems.
INVERTER IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS — This manual contains important safety and operating instructions for the Inverter. 1. Do not expose the Inverter to rain or snow unless it is a sealed model. 2. Use of an attachment not recommended or sold by the Inverter manufacturer may result in a risk of electric shock, fire, or injury to persons. 3. Do not disassemble the Inverter; take it to a qualified serviceman when service or repair is required.
TABLE OF CONTENTS • Front Cover • Product Warnings and Advisories • Table of Contents • Introduction • Box Contents • Main Parts • Operation • Indicators • Installation • DC/AC Connections • Troubleshooting • Options • Specifications • Warranty Copyright (2005-2017) Analytic Systems Ware (1993) Ltd.
Introduction The IPSi1200 series Intelligent Pure Sinewave Inverter is designed specifically for powering computers and other sensitive AC loads in rugged, mobile, off-grid environments. It produces pure sinewave AC power, identical to a conventional AC outlet. Internally, the IPSi1200 is controlled by a sophisticated Digital Signal Processor (DSP) for optimal control and the most efficient operation possible.
Main Parts 5 1 6 7 2 8 3 9 4 Front Panel 1. MicroUSB Port 6. Power Push Button 2. Positive DC Input Connection 7. Output Fuse 3. Negative DC Input Connection 8. Hard wire AC Output Connection 4. Chassis Grounding Stud 9. NEMA 5-15 AC Output Connection 5. Indicator LEDs Rear Panel (Not shown) 1.
Operation Before operating, the Inverter must be properly installed and the load(s) and batteries must be properly connected. See Installation, DC Connections, and AC connections for more information. Move the power switch to ON to energize the circuitry. The AC Power LED, Invert LED, and either the 50 Hz or 60 Hz LED will glow green indicating the presence of AC power at the output. The inverter will begin supplying the load with voltage and current printed on its label.
Installation Mounting Mount the Inverter in a WELL VENTILATED and DRY area with at least 1 inch (2.54 cm) of clearance all around the unit for adequate heat dissipation. DANGER: Do not mount the unit anywhere explosive gases can accumulate. A slight arc may form when the power leads are connected and, in the unlikely event of a failure, sparks may be generated inside the unit. CAUTION: The unit must be mounted on a flat horizontal surface.
DC Connections BEFORE MAKING ANY CONNECTIONS, MAKE THE POWER SWITCH IS OFF. DC Input Connection Before making any connections, prepare a circuit breaker or fuse-protected power DC source with a suitable rating for operation. See Specifications for more details. Two Phoenix VDFK Block Terminals are provided as DC Input Connections. • The positive DC Input connection is the RED Terminal Block.
AC Connections BEFORE MAKING ANY CONNECTIONS, MAKE THE POWER SWITCH IS OFF. AC Output Connection One standard NEMA 5-15 AC Outlet protected by a 15A circuit breaker is supplied as an AC output connection. The wiring pinout of this connection is: • Pin A - AC Hot • Pin B - AC Neutral • Pin C - AC Ground (Chassis) Three Phoenix VDFK Block Terminals are also provided as a secondary AC Output Connection.
Remote Control Port This port is intended to connect to an Analytic Systems Digital Remote Control, but can also be used for as a remote ON/OFF switch, isolated RS232 communications terminal and dry contact output fail indicator. The remote control port is a standard RJ45 style “telephone jack“ connector with Analytic Systems proprietary connections. The wire colors in the table below correspond to colors found in any standard T-568B network cable.
Off-line UPS (Optional) The Off-line UPS (Uninterrupted Power Source) option allows the Inverter to be used as a backup power source in the event of external AC power failure. AC Power Source Normal Operation • The AC power source supplies AC current to both the battery charger and the load (Running through the Inverter’s off-line). Load Inverter • Legend AC Current DC Current Battery Charger DC Power Source The battery charger supplies DC power to a battery, maintaining it at full charge.
Troubleshooting This unit features eight LED indicators and an alarm buzzer to help diagnose any malfunctions. The Inverter will sound the buzzer to alert you prior to shutting down. You should immediately check the LED indicators to determine the cause of the shutdown. LED Indicator Meaning LOW VOLTAGE The input voltage is too low for normal operation. Fix: Check that the rating of the DC power source is appropriate for the application.
InverterWizard Program The Inverter is factory preset for the input voltage, output voltage, and output frequency on the label. If these parameters are satisfactory, the Inverter can be put immediately into service. The low voltage shutdown parameters are set for the lowest battery voltage that the Inverter will support.
Specifications Input Nominal Voltage 125 VDC Actual Voltage 100 - 140 VDC Input Amps (max) 14.0 A Input Fuse None, external fuse or breaker required Input Connection 1 30 Amp, 250V Rated CSA/UL Approved Terminal Block, Red for Positive, Black for Negative Output Voltage 110 +/- 2 VAC 220 +/- 4 VAC Output Amps (cont) 11.0 A 5.5 A Output Amps (max) 14.0 A 7.0 A Output Frequency 50.00 ± 0.01 or 60.00 ± 0.01 Hz Regulation (Line & load) < +/- 2.
Limited Warranty 1. The equipment manufactured by Analytic Systems Ware (1993) Ltd. (the “Warrantor”) is warranted to be free from defects in workmanship and materials under normal use and service. 2. This warranty is in effect for: a. 3 Years from date of purchase by the end user for standard products offered in our catalog. b. 2 Years from date of manufacture for non-standard or OEM products c. 1 Year from date of manufacture for encapsulated products. 3.
DESIGNED AND MANUFACTURED BY 800-668-3884 604-946-9983 sales@analyticsystems.com Battery Chargers • Inverters • Power Supplies • Voltage Converters www.AnalyticSystems.com 8128 River Way Delta, BC V4G 1K5 | Canada Register Products Online | www.analyticsystems.