INSTALLATION & OPERATION MANUAL IPSi3600 PURE-SINE INVERTER An ISO9001 and AS9100 Registered Company Battery Chargers • Inverters • Power Supplies • Voltage Converters 8128 River Way, Delta B.C. V4G 1K5 Canada T. 604.946.9981 F. 604.946.9983 TF. 800.668.3884 (US/CANADA) www.analyticsystems.
IMPORTANT & SAFETY INSTRUCTIONS 1. SAVE THESE INSTRUCTIONS — This manual contains important safety and operating instructions for the inverter. 2. Do not expose the inverter to rain or snow. 3. Use of an attachment not recommended or sold by the inverter manufacturer may result in a risk of fire, electric shock, or injury to persons. 4. Do not disassemble the inverter; take it to a qualified serviceman when service or repair is required. Incorrect reassembly may result in a risk of electric shock or fire.
Introduction The IPSi3600 Series 3600 Watt ‘Pure Sine Wave’ Inverter is designed specifically for running sensitive electronic equipment. It produces pure sine wave AC power exactly the same as a regular AC outlet. The IPSi3600 Inverter is controlled by a sophisticated Digital Signal Processor (DSP) for optimal control and the most efficient operation possible.
Specifications Electrical (Input) Nominal (ip) 24, 28, 32 or 36 VDC 48 or 72 VDC Actual (Vdc) 20 - 45 40 - 80 Input Amps (max) 180 90 Electrical (Output) Output Volts Nominal 110 VAC 220 VAC Output Amps Actual (AC) 110 ± 10 VAC (user adjustable) 220 ± 20 VAC (user adjustable) Output Amps 30A (cont) / 36A (peak) 15A (cont) / 18A (peak) Output Frequency 50.00 or 60.00 Hz ± 0.
Designed and manufactured by: ANALYTIC SYSTEMS WARE (1993) LTD. 8128 River Way Delta, BC V4G 1K5 Canada www.analyticsystems.com p. 604.946.9981 f. 604.946.9983 tf. 800.668.3884 US/Canada info@analyticsystems.com Revised February 2016 Installation MOUNTING Mount the unit in a DRY location. Mount the unit in a ventilated area. Allow at least 1 inch of clearance around the unit for adequate cooling.
OUTPUT CONNECTIONS Two standard circuit breaker protected 20 Amp AC receptacles are provided for connection. In addition a 30 amp, 250V rated CSA/UL approved terminal block is provided for wiring to a distribution panel. This terminal block is NOT circuit breaker protected so each device wired to the distribution panel must have its own breaker. Ensure that the total average load of all the devices does not exceed the continuous current rating of the unit. CAUTION: Do not apply AC voltage to the outlets.
There are 8 LED indicators labelled 1 through 8. Their functions are as follows: 1. Low Input Voltage: Blinks Red when the input voltage is near the lower limit for proper operation. Glows Red when the input voltage is too low for proper operation and will be accompanied by the Bypass LED glowing Red and the On/Off switch will not be glowing. Check for the reason for low voltage. 2. High Input Voltage: Blinks Red when the input voltage is near the upper limit for proper operation.
Limited Warranty 1. The equipment manufactured by Analytic Systems Ware (1993) Ltd. (the “Warrantor”) is warranted to be free from defects in workmanship and materials under normal use and service. 2. This warranty is in effect for 3 years from the date of purchase by the end user. 3. Analytic Systems will determine eligibility for warranty from the date of purchase shown on the warranty card when returned within 30 days, or a. The date of shipment by Analytic Systems, or b.