INSTALLATION & OPERATION MANUAL PWS1000 Power Supply An ISO9001 and AS9100 Registered Company Battery Chargers • Inverters • Power Supplies • Voltage Converters 8128 River Way, Delta B.C. V4G 1K5 Canada T. 604.946.9981 F. 604.946.9983 TF. 800.668.3884 (US/CANADA) www.analyticsystems.
Copyright (2005-2013) Analytic Systems Ware (1993) Ltd.
IMPORTANT & SAFETY INSTRUCTIONS 1. SAVE THESE INSTRUCTIONS — This manual contains important safety and operating instructions for power supply. 2. Do not expose power supply to rain or snow. 3. Use of an attachment not recommended or sold by the power supply manufacturer may result in a risk of fire, electric shock, or injury to persons. 4. Do not disassemble power supply; take it to a qualified serviceman when service or repair is required.
Introduction All new Current Mode switching design offers increased power and reliability in a compact package. Extra input and output filtering reduce EMI to extremely low levels. Reliability features include an input fuse, thermal shutdown, current limiting and output short circuit shutdown with automatic recovery. The output voltage is easily adjusted 1.0 volts above or below the standard output voltage. The model PWS1000 Power Supply supplies either 12, 24 or 48 VDC from a 110 or 220 VAC power source.
General Input Frequency 45 - 65 Hz Noise on Input < 50 milli-Volts Noise on Output < 50 milli-Volts Transient Response < 1 V for 50% surge Efficiency > 80 % @ maximum output Temp. Range -25 to +40 deg. C @ maximum output Isolation Input-Output & Input-Case 1500 Vdc Output-Case 500 VDC (1500Vdc @ 48 V Out) Isolation Output-Case 500VDC Length 14.5 in / 36.8 cm Width 10.2 in / 29.9 cm Height 5.5 in / 14.0 cm Clearance 1 Inch (2.
All connections should be made inside an appropriate junction box. The maximum current draw from the 110 VAC supply is 14.6 amps, so a 20 amp circuit breaker should be used in the circuit panel and for a 220 VAC supply, 7.3 amps is the maximum current draw, so a 10 amp circuit breaker should be used in the circuit panel to feed power to the PWS1000. OUTPUT CONNECTIONS Two Positive output terminals and two Negative output terminals are provided. Connect only one wire to each terminal.
Meters High quality digital meters can be added to the charger (factory installed only). Both outputs can be monitored for current and voltage. LOAD SHARE OPTION OUTPUT 1 OUTPUT 2 OUTPUT 1 OUTPUT 2 The units may be configured for load sharing if they are equiped with the optional output isolation diodes. To confirm that your unit has these diodes, use an ohmmeter to measure the resistance between the two positive output terminals. If the diodes are present the terminals will measure as not connected.
Remote Control Option IMPORTANT: This remote is to be used only on Power Supplies manufactured by Analytic Systems. A remote control panel may be connected to the converter using a 9-pin D-connector, which attaches to the side of the converter. The remote control panel and D connector are part of the remote control option. The remote control panel allows the unit to be operated remotely as well as duplicating all the diagnostic indicators and audible alarm.
Troubleshooting This unit provides LED indicators and a buzzer to help diagnose any problems. The unit should sound the buzzer to alert you prior to shutting itself down. You should immediately check the indicators to determine the cause of the shutdown.
Special Services & Options Conformal Coating INCLUDED ON ALL UNITS UNLESS REQUESTED NOT TO as of April 1, 2014 Option “c” Ruggedization Package (EXTRA Conformal Coating and RTV Compound) Option “v” Marine / Industrial Pkg (EXTRA Conformal dipping and RTV Compound) Option “MS” Military Pkg (incl.
Limited Warranty 1. The equipment manufactured by Analytic Systems Ware (1993) Ltd. (the “Warrantor”) is warranted to be free from defects in workmanship and materials under normal use and service. 2. This warranty is in effect for: a. 3 Years from date of purchase by the end user for standard products offered in our catalog. b. 2 Years from date of manufacture for non-standard or OEM products c. 1 Year from date of manufacture for encapsulated products. 3.
An ISO9001 and AS9100 Registered Company Battery Chargers • Inverters • Power Supplies • Voltage Converters 8128 River Way, Delta B.C. V4G 1K5 Canada T. 604.946.9981 F. 604.946.9983 TF. 800.668.3884 (US/CANADA) www.analyticsystems.