Installation guide

SECTION XX XXXXXXXXX
26
SECTION 3 INSTALLATION
26
Terminal Positions with Minimum Distance mm
A Directly below an opening, air brick, opening window etc. 300
B Above an opening, air brick, opening window etc 300
C Horizontal to an opening, air brick, opening window etc. 300
D Below a gutter or sanitary pipework 75
E Below the eaves 200
F Below a balcony or carport roof 200
G Above ground, roof or balcony level 300
H From vertical drain/soil pipework 150
J From an internal or external corner 300
K From a surface or boundary facing the terminal 600
L Vertically from a terminal on the same wall 1500
M Horizontally from a terminal on the same wall (30 & 60kW) 300
(90 & 120kW) 600
N From a terminal facing the terminal 1200
P From an opening in a carport (e.g. door, windows) into the building 1200
Q Above roof 500
R From a vertical structure on a roof 500
S Above flat roof 1000
FLUE SYSTEMS
Fig 11