Installation guide
TECHNICAL DATA SECTION 2
Hi-Flo
RANGE
5
Storage Capacity l 145 295 386 282 245
gal 32 65 81 62 54
Recovery thro' 44ºC/80ºF l/h 649 788 1140 1403 1812
gal/h 143 169 251 309 399
Recovery thro' 56ºC/100ºF l/h 517 613 913 1122 1449
gal/h 114 135 201 247 319
Recovery thro' 72ºC/130ºF l/h 399 472 699 862 1117
gal/h 88 104 154 190 246
Heat Input Gross kW 41.8 49 76 92.5 122
Btu/h
142.622 167,188 259,312 315,610 416,264
Heat Input Net kW 38 44 69 84 111
Btu/h
129,656 150,128 235,428 286,608 378,732
Gas LPG CAT I
3
mbar 37 37 37 37 37
Inlet Gas Pressure
ins wg. 14.86 14.86 14.86 14.86 14.86
mbar 28 28 28 28 28
ins wg. 11.26 11.26 11.26 11.26 11.26
Gas Flow Rate Propane m
3
/h 1.61 1.89 2.93 3.58 4.71
ft
3
/h 57 66.87 103.7 126.25 166.50
Gas Flow Rate Butane m
3
/h 1.26 1.48 2.29 2.79 3.68
ft
3
/h 44.6 52.24 81.04 98.63 130.08
Gas Connection Rc (in BSP Int) 3/4 3/4 3/4 3/4 3/4
Flue Gas Temp ºC 125 125 170 190 170
Flue Gas Volume m
3
/h 57 67 104 126 167
Gas Injector Orifice Diameter mm 1.60 1.70 1.85 1.78 1.78
in 0.063 0.067 0.073 0.070 0070
Flue Size (Secondary) mm 150 150 200 200 250
in 6 6 8 8 10
Cold Water Feed Connection R (in BSP/Exl) 11/2 11/2 11/2 11/2 11/2
Hot Water Flow Connection R (in BSP/Exl) 11/2 11/2 11/2 11/2 11/2
*Return Connection Rp (in BSP/Int) 3/4 3/4 3/4 3/4 3/4
Drain Port Size R (in BSP/Ext) 3/4 3/4 3/4 3/4 3/4
Max. Working Pressure bar 10.3 10.3 10.3 10.3 10.3
lbf/in
2
150 150 150 150 150
Max. Test Pressure bar 20 20 20 20 20
lbf/in
2
300 300 300 300 300
Weight Empty kg 190 200 289 294 269
lb 419 441 687 515 594
Weight Full kg 335 488 656 618 514
lb 738 1091 1447 1135 1134
Shipping Weight kg 199 230 316 287 293
lb 438 492 697 566 645
Shipping Dimensions Depth mm 902 914 914 914 914
in 35 1/2 36 36 36 36
Shipping Dimensions Width mm 768 762 762 762 762
in 30 1/4 30 30 30 30
Shipping Dimensions Height mm 1270 1960 2210 1960 1960
in 50 77 87 77 77
ANDREWS MODEL NO.
L32/143 L65/169 L81/251 L62/309 L54/399
Propane
Butane
* If the water heater is to be
used on an unvented system,
the combined temperature/
pressure relief valve must be
fitted directly into the tank.
The secondary return is then
connected to the drain port
via a suitable tee.