RF11–IOM–001 2/13 AIR FLO W SO LUTIO NS RF-1 1 Ins tal l ati o n, O per ati o n, and Mai ntenanc e Sl i p-In Var i abl e Ai r Vo l ume Ter mi nal s
1220 Watson Center Road • Carson, CA 90745 Tel: (310) 835-7500 • Fax: (310) 835-0448 www.anemostat.com • air@anemostat.com Contents Model Number Description ...........................................................................................................................................................3 Unit Labeling...................................................................................................................................................................................
1220 Watson Center Road • Carson, CA 90745 Tel: (310) 835-7500 • Fax: (310) 835-0448 www.anemostat.com • air@anemostat.com Model Number Description Typical String: RF11 / 12.00 / 12.
1220 Watson Center Road • Carson, CA 90745 Tel: (310) 835-7500 • Fax: (310) 835-0448 www.anemostat.com • air@anemostat.com Unit Labeling Labels are applied to each terminal as follows: • Unit specific nameplate showing model number, manufactured date, and information regarding controls and heat provided as appropriate. • The appropriate airflow calibration chart indicating the airflow at varying airflow sensor signals as shown on pages 8, 9, and 10.
1220 Watson Center Road • Carson, CA 90745 Tel: (310) 835-7500 • Fax: (310) 835-0448 www.anemostat.com • air@anemostat.com Receiving and Inspection Instructions • Check the bill of lading to verify receipt of all listed items (including any loose accessory items). Notify the carrier and the local ANEMOSTAT representative of any shortages or items shipped in error. • Thoroughly examine all units for transportation damage (dents, punctures, etc).
1220 Watson Center Road • Carson, CA 90745 Tel: (310) 835-7500 • Fax: (310) 835-0448 www.anemostat.com • air@anemostat.com Unit Placement and Installation 1. The RF-11 is a VAV air terminal unit – it is designed to slip into the side of square or rectangular HVAC duct to provide air flow control thru the duct.
1220 Watson Center Road • Carson, CA 90745 Tel: (310) 835-7500 • Fax: (310) 835-0448 www.anemostat.com • air@anemostat.com Clearance Requirements • Line voltage and low voltage electrical enclosures must have adequate clearances to meet requirements of NFPA 70 (NEC). This is typically 36" minimum. Note that additional clearance requirements may be required by local codes or building construction specifications.
1220 Watson Center Road • Carson, CA 90745 Tel: (310) 835-7500 • Fax: (310) 835-0448 www.anemostat.com • air@anemostat.com Airflow Sensor ∆P Versus Airflow SIGNAL PRESSURE: INCH WATER ") 8L SIZ E( (16 3 CF M@ 1 2) 3) 6 5) (9 8 (11 7L 4L 6L 1.0 .9 .8 .7 .6 5L (4 1 (6 6 0) (75 6) 9) ) (30 3 3L 2L 1L (19 0 ) C23 / C24 / C31 Series Pneumatic Controls & DDC Controls* .5 .4 .3 .2 .1 .09 .08 .07 .06 .05 .
20000 10000 9000 8000 7000 6000 5000 SIZ E (CF M@ 1 ") 200000 100000 90000 80000 70000 60000 50000 40000 30000 20000 10000 9000 8000 7000 6000 5000 4000 3000 2000 1000 900 800 700 600 FLOW RATE: CFM 4000 (3 8 5 (43 0) 2 (5 1 2 ) 0 (5 8 0 ) (63 42) 8 (74 9) 85 (8 5 ) 8 0) (1 0 48 6 SH ) NH (12 3 (14 93) 44 8 ) OH (2 1 9 26 ) FLOW RATE: CFM 3000 2000 1000 900 800 700 600 500 400 1.0 .9 .8 .7 .
1220 Watson Center Road • Carson, CA 90745 Tel: (310) 835-7500 • Fax: (310) 835-0448 www.anemostat.com • air@anemostat.com Altitude Correction Factors Barometric Pressure (in h.g.) Altitude (feet) Density lb/ft3 Correction Factor 29.92 20.28 28.85 28.33 27.82 27.32 26.81 26.33 25.84 25.37 24.89 24.44 23.98 23.54 23.09 0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 6500 7000 .075 .074 .072 .071 .070 .068 .067 .066 .065 .064 .062 .061 .060 .059 .058 1.03 1.01 0.99 0.98 0.96 0.95 0.93 0.