Instructions

Anybus Communicator - EtherNet/IP Interface Installation Sheet
www.anybus.comSP0904, rev. 1.10, Mar 2015
1
3
5
2
4
6
Module Front
1
9
5
6
1
2
4
1
Bottom View
Subnetwork Connector
Pin no. Description
1 +5V OUT
2 RS232 Rx
3 RS232 Tx
4NC
5 Signal GND
6 RS422 Rx+
7 RS422 Rx-
8 RS485+ / RS422 Tx+
9 RS485- / RS422 Tx-
PC Connector:
1. GND
2. GND
3. RS232 Rx
4. RS232 Tx
Power:
1. +24 V DC
2. GND
Accessories Checklist
The following items are required for installation:
Anybus Communicator Resource CD (Includes con guration
software, manuals and application notes)
• RS232 con guration cable
• Subnetwork connector
Ethernet cable and connector (not included)
Installation and Startup Summary
Mount the Communicator on the DIN-rail.
Connect the Communicator to the Ethernet/IP network.
Connect the Communicator to the subnetwork.
Connect the con guration cable between the Communicator
and the PC containing the Anybus Con guration Manager
software (ACM).
Power on the Communicator (+24 V DC).
• Con gure the Communicator using ACM.
Include the Anybus Communicator EDS le in the
Ethernet/IP con guration tool.
• Con gure and start the Ethernet/IP network.
Further information and documents about this product can be
found at the product pages on www.anybus.com.
Ethernet/IP Connectors
Pin no Description
1 TD+
2 TD-
3 RD+
4 Termination
5 Termination
6 RD-
7 Termination
8 Termination
18
LED Indicators
LED Indication Description
1 (Module Status) Off
Green
Flashing Green
Flashing Red
Red
Flashing Green/Red
No power
Controlled by a scanner in run state
Not con gured, or scanner in idle state
Minor fault (recoverable)
Major fault (unrecoverable)
Self-test in progress
2 (Network Status) Off
Green
Flashing Green
Red
Flashing Red
Flashing Green/Red
No IP address, or no power
Online, one or more EtherNet/IP connec-
tions established
Online, no connections established
Duplicate IP address detected. Fatal error.
One or more connections timed out
Self-test in progress
3 (Link) Off
Green
No link
Connected to an Ethernet network
4 (Activity) Off
Flashing Green
No Ethernet activity
Activity, receiving/transmitting Ethernet
packets
5 (Subnet Status) Flashing green
Green
Red
Running, but one or more transaction errors
Running
Transaction error/timeout or subnet stopped
6 (Device Status) Off
Alternating red/green
Green
Flashing green
Red
Flashing red
Power off
Invalid or missing con guration
Initializing
Running
Bootloader mode
Note the ash sequence pattern and contact
HMS support

Summary of content (2 pages)