10.1.3. Choose Serial Protocol Type
The Temperature Regulator is using a request/response protocol to access parameters addressed with index and
sub index.
Figure 81. Communicaon page, Modbus RTU
On the Serial RS232/485 page, select Modbus RTU.
10.1.4. Setup Serial Communicaon
Set up the communicaon between the Communicator and the Temperature Regulator.
In the Serial RS232/485 page, congure the Communicaon sengs.
Figure 82. Serial RS232/485, Basic sengs
Table 2. Used the following sengs:
Frame objects Value
Physical standard RS-232
Baud rate 19200 baud
Data bits 8 bits
Parity None
Stop bits 2 stop bit
Anybus
®
Communicator
- PROFIBUS to Modbus RTU/Serial Temperature Regulator - Modbus RTU Use Case