Instructions
Table Of Contents
- Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial
- Table of Contents
- 1. Preface
- 2. Safety
- 3. Preparation
- 4. About Anybus Communicator
- 5. Installation
- 6. Configuration Quick Guide
- 7. Communicator Configuration
- 7.1. Connect the Communicator
- 7.2. Access the Built-In Web Interface From HMS IPconfig
- 7.3. Access the Built-In Web Interface From a Web Browser
- 7.4. Communicator Built-In Web Interface Overview
- 7.5. General Subnetwork Settings
- 7.6. About Transaction Templates
- 7.7. Build Transaction Template
- 7.8. Nodes and Transactions
- 7.9. High Level Network Settings
- 7.10. I/O Data Map
- 7.11. Apply Configuration
- 7.12. To Use an Existing Configuration
- 7.13. To Use an Communicator Classic Configuration
- 8. PLC Configuration
- 9. Verify Operation
- 10. Use Cases
- 11. Maintenance
- 12. Troubleshooting
- 13. Technical Data
- 14. Reference Guides
10.2.6. Setup Node and Transacons
Figure 92. My Drive node with transacons
1. Add a node and select it.
2. In Node sengs congure the node with the following sengs:
Node sengs Value
Node address 1
My Drive is set up as a node with Node address 1.
Name My Drive
Timeout me 1000 ms (default)
Reconnecng me 1000 ms (default)
Retries 0 (default)
3. Add four transacons to the My Drive node and congure them with the following sengs:
Table 10. My Drive contains the following parameters
Transacon name Transacon template Index Sub index
Control Word Write Parameter (0x02) 1 1
Speed Write Parameter (0x02) 1 2
Status Word Read Parameter (0x01) 2 1
Actual Speed Read Parameter (0x01) 2 2
AC Motor Drive - Custom Request/Response Use Case Anybus
®
Communicator
™
- PROFIBUS to Modbus RTU/Serial
SCM-1202-177 1.2 Page 109 of 134