Instructions
Table Of Contents
- Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial
- Table of Contents
- 1. Preface
- 2. Safety
- 3. Preparation
- 4. About Anybus Communicator
- 5. Installation
- 6. Configuration Quick Guide
- 7. Communicator Configuration
- 7.1. Connect the Communicator
- 7.2. Access the Built-In Web Interface From HMS IPconfig
- 7.3. Access the Built-In Web Interface From a Web Browser
- 7.4. Communicator Built-In Web Interface Overview
- 7.5. General Subnetwork Settings
- 7.6. About Transaction Templates
- 7.7. Build Transaction Template
- 7.8. Nodes and Transactions
- 7.9. High Level Network Settings
- 7.10. I/O Data Map
- 7.11. Apply Configuration
- 7.12. To Use an Existing Configuration
- 7.13. To Use an Communicator Classic Configuration
- 8. PLC Configuration
- 9. Verify Operation
- 10. Use Cases
- 11. Maintenance
- 12. Troubleshooting
- 13. Technical Data
- 14. Reference Guides
Example 2. To set the node address 12 hex = 18 dec
1. The rear rotary switch A is not used, ensure that it is set to 0.
2. Set the center rotary switch B to 1 hex.
3. Set the front rotary switch C to 2 hex.
The center rotary switch B 1 hex = 1 dec and the front rotary switch C 2 hex = 2 dec.
The node address expressed in decimal numbers is therefore 16 x 1 + 2 = 18.
Example 3. To set the node address 7E hex = 126 dec
• The rear rotary switch A is not used, ensure that it is set to 0.
• Set the center rotary switch B to 7.
• Set the front rotary switch C to E.
The center rotary switch B 7 hex = 7 dec and the front rotary switch C E hex = 14 dec.
The node address expressed in decimal numbers is therefore 16 x 7 + 14 = 126.
Anybus
®
Communicator
™
- PROFIBUS to Modbus RTU/Serial Rotary Switch Sengs
Page 20 of 134 SCM-1202-177 1.2