Instructions
Table Of Contents
- Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial
- Table of Contents
- 1. Preface
- 2. Safety
- 3. Preparation
- 4. About Anybus Communicator
- 5. Installation
- 6. Configuration Quick Guide
- 7. Communicator Configuration
- 7.1. Connect the Communicator
- 7.2. Access the Built-In Web Interface From HMS IPconfig
- 7.3. Access the Built-In Web Interface From a Web Browser
- 7.4. Communicator Built-In Web Interface Overview
- 7.5. General Subnetwork Settings
- 7.6. About Transaction Templates
- 7.7. Build Transaction Template
- 7.8. Nodes and Transactions
- 7.9. High Level Network Settings
- 7.10. I/O Data Map
- 7.11. Apply Configuration
- 7.12. To Use an Existing Configuration
- 7.13. To Use an Communicator Classic Configuration
- 8. PLC Configuration
- 9. Verify Operation
- 10. Use Cases
- 11. Maintenance
- 12. Troubleshooting
- 13. Technical Data
- 14. Reference Guides
In the PLC program:
1. Import product le
Opon if the PLC program requires a GSD (General Staon Descripon) le.
Import the GSD le into your PLC project.
2. Congure the communicaon
Congure the PLC to communicate with the Communicator according to the I/O data map created in the
Communicator.
Anybus
®
Communicator
™
- PROFIBUS to Modbus RTU/Serial PLC Conguraon
Page 36 of 134 SCM-1202-177 1.2