Instructions

Table Of Contents
Limit
NOTE
Limit can only be added as a Response frame eld.
Name: You can name the Frame Field to make it easier to idenfy.
Type: Specify the number of bytes in the frame. Select Byte (1 byte) (Default), Word (2 bytes), Double word (4
bytes).
Endianess: Select Big-endian (Default) or Lile-endian.
Min value: The lowest value of the limit range.
Max value: The highest value of the limit range.
Base number system: Select Decimal Dec (Default) or Hexadecimal Hex.
Data
Name: You can name the Frame Field to make it easier to idenfy.
Fixed eld*: Select Yes, set here (Default) or No, set when used.
Length: Enter a value between 1 (Default) and 512 bytes.
Min length: Specify the minimum length that can be set when the template is used.
Max length: Specify the maximum length that can be set when the template is used.
Default length: Specify the default length that can be set when the template is used.
Variable data
Name: You can name the Frame Field to make it easier to idenfy.
Fixed eld*: Select Yes, set here (Default) or No, set when used.
Minimum payload length: Specify the minimum payload length that can be set when the template is used.
Maximum payload length: Specify the maximum payload length that can be set when the template is used.
Default max payload length: Specify the default payload length that can be set when the template is used.
Data delimiter: Specify how to detect/dene the length of the variable data of the high level network. Select
Byte counter, End paern or None (Default).
For informaon about End- and Length character, see Data Delimiter and Subnet Delimiter Opons (page 62).
Subnet delimiter: Specify how to detect/dene the length of the variable data of the serial subnetwork. Select
Byte counter, End paern or None (Default).
For informaon about End- and Length character, see Data Delimiter and Subnet Delimiter Opons (page 62).
End paern: Specify the value dening the end of the payload, when a delimiter is set to end paern.
Fill padding: Fill up unused data mapped to the high level network or the general area with a eld padding
value.
To deacvate/acvate Fill padding, click the slide toggle. When Fill padding is acvated, enter a Fill padding
value between 0 and 255.
Base number system: Select Decimal Dec (Default) or Hexadecimal Hex.
Checksum
Name: You can name the Frame Field to make it easier to idenfy.
Checksum type: Specify the algorithm used to calculate the checksum. Select CRC (CRC-16-IBM) (Default), LRC
(ISO 1155:1978), XOR or ADD.
Start oset: Specify the oset from where to start the checksum calculaon. Enter a value between 0 (Default)
and 511.
Build Transacon Template Anybus
®
Communicator
- PROFIBUS to Modbus RTU/Serial
SCM-1202-177 1.2 Page 61 of 134