Instructions
Table Of Contents
- Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial
- Table of Contents
- 1. Preface
- 2. Safety
- 3. Preparation
- 4. About Anybus Communicator
- 5. Installation
- 6. Configuration Quick Guide
- 7. Communicator Configuration
- 7.1. Connect the Communicator
- 7.2. Access the Built-In Web Interface From HMS IPconfig
- 7.3. Access the Built-In Web Interface From a Web Browser
- 7.4. Communicator Built-In Web Interface Overview
- 7.5. General Subnetwork Settings
- 7.6. About Transaction Templates
- 7.7. Build Transaction Template
- 7.8. Nodes and Transactions
- 7.9. High Level Network Settings
- 7.10. I/O Data Map
- 7.11. Apply Configuration
- 7.12. To Use an Existing Configuration
- 7.13. To Use an Communicator Classic Configuration
- 8. PLC Configuration
- 9. Verify Operation
- 10. Use Cases
- 11. Maintenance
- 12. Troubleshooting
- 13. Technical Data
- 14. Reference Guides
7.9. High Level Network Sengs
Congure the PROFIBUS network sengs.
7.9.1. To Use Automac I/O Sizes
Figure 57. PROFIBUS, I/O sizes
By default, the Communicator is set to use automac I/O sizes.
The size of the input data, Data Size to PROFIBUS, and the output data, Data Size from PROFIBUS, is determined
by the subnetwork conguraon.
In the Communicator built-in web interface, the Use Automac I/O Sizes checkbox is selected.
7.9.2. To Congure I/O Sizes Manually
NOTE
The maximum data size in each direcon is 244 bytes.
Figure 58. PROFIBUS, I/O sizes
1. Deselect the Use Automac I/O Sizes checkbox.
2. Enter a value for Data Size to PROFIBUS and a value for Data Size from PROFIBUS.
Anybus
®
Communicator
™
- PROFIBUS to Modbus RTU/Serial High Level Network Sengs