Instructions
Table Of Contents
- Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial
- Table of Contents
- 1. Preface
- 2. Safety
- 3. Preparation
- 4. About Anybus Communicator
- 5. Installation
- 6. Configuration Quick Guide
- 7. Communicator Configuration
- 7.1. Connect the Communicator
- 7.2. Access the Built-In Web Interface From HMS IPconfig
- 7.3. Access the Built-In Web Interface From a Web Browser
- 7.4. Communicator Built-In Web Interface Overview
- 7.5. General Subnetwork Settings
- 7.6. About Transaction Templates
- 7.7. Build Transaction Template
- 7.8. Nodes and Transactions
- 7.9. High Level Network Settings
- 7.10. I/O Data Map
- 7.11. Apply Configuration
- 7.12. To Use an Existing Configuration
- 7.13. To Use an Communicator Classic Configuration
- 8. PLC Configuration
- 9. Verify Operation
- 10. Use Cases
- 11. Maintenance
- 12. Troubleshooting
- 13. Technical Data
- 14. Reference Guides
7.10.1. Opmize the I/O Data Map
The opmize funcon is used to automacally remove gaps between the mapping.
IMPORTANT
Opmize remove gaps between the data objects in the map and should be used with care on
already commissioned systems. Expected mapping in the PLC may change.
NOTE
If you opmize the I/O data map, the current I/O data map will be overwrien.
Figure 61. I/O data map page, Opmize
To opmize the map:
1. Click Opmize.
2. To conrm, click OK.
I/O Data Map Anybus
®
Communicator
™
- PROFIBUS to Modbus RTU/Serial
SCM-1202-177 1.2 Page 79 of 134