7.10.3. Map Area
Figure 64. I/O data map page, Map area opons
Map area opons
You must specify the map area to use for each transacon in the I/O data map.
Select one of the following Map area opons:
Input/Output: The transacon data is sent/recieved to/from the high level network.
General: This area is used for transferring transacon data between individual nodes on the subnetwork.
When General is selected, the transacon data cannot be accessed from the high level network.
Unmapped: The transacon data is not used.
Start address
For Input/Output and General, you can enter a start address for the transacon data.
7.10.4. Trigger Byte
Trigger byte is used to enable/disable the trigger funconality for the response.
When Trigger byte is enabled, the Communicator increases the trigger byte by one when the Communicator
receives new data from the subnetwork.
The Trigger byte is stored in the Data from PROFIBUS area or the General area.
The locaon of the trigger byte is specied by the address.
Figure 65. I/O data map
I/O Data Map Anybus
®
Communicator
- PROFIBUS to Modbus RTU/Serial
SCM-1202-177 1.2 Page 81 of 134