Instructions
Table Of Contents
- Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial
- Table of Contents
- 1. Preface
- 2. Safety
- 3. Preparation
- 4. About Anybus Communicator
- 5. Installation
- 6. Configuration Quick Guide
- 7. Communicator Configuration
- 7.1. Connect the Communicator
- 7.2. Access the Built-In Web Interface From HMS IPconfig
- 7.3. Access the Built-In Web Interface From a Web Browser
- 7.4. Communicator Built-In Web Interface Overview
- 7.5. General Subnetwork Settings
- 7.6. About Transaction Templates
- 7.7. Build Transaction Template
- 7.8. Nodes and Transactions
- 7.9. High Level Network Settings
- 7.10. I/O Data Map
- 7.11. Apply Configuration
- 7.12. To Use an Existing Configuration
- 7.13. To Use an Communicator Classic Configuration
- 8. PLC Configuration
- 9. Verify Operation
- 10. Use Cases
- 11. Maintenance
- 12. Troubleshooting
- 13. Technical Data
- 14. Reference Guides
3. Select the swapping type from the Endian swap drop-down menu.
Seng Descripon
No swapping Default seng
No swapping is performed on the data.
Byte swap Swap 2 bytes
A B C D becomes B A D C
Word swap Swap 4 bytes
A B C D becomes C D A B
Byte and Word swap A B C D becomes D C B A
4. To apply the sengs, click Apply in the web-interface header, and follow the instrucons.
7.10.6. Oine Opon
Figure 67. I/O data map page, Oine opons
Oine mode is used to dene what data to send if the network connecon or connecon with a specic node is
lost.
You must specify the oine mode to use for each transacon on the I/O data map.
Select one of the following Oine opons:
• Clear (Default): The data is cleared and the value 0 is sent.
• Freeze: The Communicator holds the value unl the connecon is restored.
• No scanning: Stop sending this transacon on the sub-network. This opon is only valid for produce and
request transacons.
I/O Data Map Anybus
®
Communicator
™
- PROFIBUS to Modbus RTU/Serial
SCM-1202-177 1.2 Page 83 of 134