Instructions
Table Of Contents
- Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial
- Table of Contents
- 1. Preface
- 2. Safety
- 3. Preparation
- 4. About Anybus Communicator
- 5. Installation
- 6. Configuration Quick Guide
- 7. Communicator Configuration
- 7.1. Connect the Communicator
- 7.2. Access the Built-In Web Interface From HMS IPconfig
- 7.3. Access the Built-In Web Interface From a Web Browser
- 7.4. Communicator Built-In Web Interface Overview
- 7.5. General Subnetwork Settings
- 7.6. About Transaction Templates
- 7.7. Build Transaction Template
- 7.8. Nodes and Transactions
- 7.9. High Level Network Settings
- 7.10. I/O Data Map
- 7.11. Apply Configuration
- 7.12. To Use an Existing Configuration
- 7.13. To Use an Communicator Classic Configuration
- 8. PLC Configuration
- 9. Verify Operation
- 10. Use Cases
- 11. Maintenance
- 12. Troubleshooting
- 13. Technical Data
- 14. Reference Guides
8.3. How to Use GSD File Modules
When conguring the PROFIBUS communicaon, ensure that the I/O sizes in the PROFIBUS master match the I/O
sizes se on the Communicator PROFIBUS page, see High Level Network Sengs (page 76).
Import the Communicator GSD le into TIA portal and combine the modules to get the correct I/O size.
NOTE
Fill unused module slots with the value Empty.
Table 1. Modules available in the Communicator GSD le
Mod_name Cong Module-Reference In/Out Size
Empty module 0x00 1 N/A 0
1 byte input module 0x90 2 In 1 byte
2 bytes input module 0xD0 3 In 1 word (2 bytes)
4 bytes input module 0xD1 4 In 2 words (4 bytes)
8 bytes input module 0xD3 5 In 4 words (8 bytes)
16 bytes input module 0xD7 6 In 8 words (16 bytes)
32 bytes input module 0xDF 7 In 16 words (32 bytes)
64 bytes input module 0x40, 0xDF 8 In 32 words (64 bytes)
128 bytes input module 0x40, 0xFF 9 In 64 words (128 bytes)
1 byte output module 0xA0 10 Out 1 byte
2 bytes output module 0xE0 11 Out 1 word (2 bytes)
4 bytes output module 0xE1 12 Out 2 words (4 bytes)
8 bytes output module 0xE3 13 Out 4 words (8 bytes)
16 bytes output module 0xE7 14 Out 8 words (16 bytes)
32 bytes output module 0xEF 15 Out 16 words (32 bytes)
64 bytes output module 0x80, 0xDF 16 Out 32 words (64 bytes)
128 bytes output module 0x80, 0xFF 17 Out 64 words (128 bytes)
Example 8. How to combine modules
In this example we congure the following sizes:
• Data size to PROFIBUS: 95 bytes
Combine modes: 64 + 16 + 8 + 4 + 2 + 1
Size: [ 0xDF + 0xD7 + 0xD3 + 0xD1 + 0xD0 + 0x90 ]
• Data size from PROFIBUS: 58 bytes
Combine modes: 32 + 16 + 8 + 2
Size: [ 0xEF + 0xE7 + 0xE3 + 0xE0 ]
Anybus
®
Communicator
™
- PROFIBUS to Modbus RTU/Serial How to Use GSD File Modules