Example 9. Fill unused module slots
The gateway cannot move posions and it expects data of a certain size at each posion between the combine
modes.
Therefore, unused module slots needs to be lled with the value Empty.
In this example we use an I/O size of 35 bytes.
Combine modes: 1 + 2 + 32
To ll the posions, we add Empty where the Combine modes 4, 8, 16, 64 and 128 are expected.
1 byte + 2 bytes + Empty + Empty + Empty + 32 bytes + Empty + Empty
Figure 77. Example, ll unused module slots in TIA Portal
How to Use GSD File Modules Anybus
®
Communicator
™
- PROFIBUS to Modbus RTU/Serial
SCM-1202-177 1.2 Page 93 of 134