ENGLISH Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial STARTUP GUIDE SP2980 Version 1.
Important User Information Disclaimer The information in this document is for informational purposes only. Please inform HMS Networks of any inaccuracies or omissions found in this document. HMS Networks disclaims any responsibility or liability for any errors that may appear in this document. HMS Networks reserves the right to modify its products in line with its policy of continuous product development.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Preface 1. Preface 1.1. About This Document This document describes how to install Anybus® Communicator™. For additional documentation and software downloads, FAQs, troubleshooting guides and technical support, please visit www.anybus.com/support. 1.2. Document Conventions Safety Symbols DANGER Instructions that must be followed to avoid an imminently hazardous situation which, if not avoided, will result in death or serious injury.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Trademarks Information Symbols NOTE Additional information which may facilitate installation and/or operation. TIP Helpful advice and suggestions. 1.3. Trademarks Anybus® is a registered trademark of HMS Networks. All other trademarks are the property of their respective holders. Page 2 of 28 SP2980 1.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Safety 2. Safety 2.1. Intended Use The intended use of this equipment is as a communication interface and gateway. The equipment receives and transmits data on various physical layers and connection types. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. 2.2. General Safety CAUTION Ensure that the power supply is turned off before connecting it to the equipment.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Preparation 3. Preparation 3.1. Cabling Have the following cables available: • Ethernet cable for configuration • PROFIBUS cable for connecting to the high level network • Power cable 3.2. Tools Have the following tools available: • Flat-head screwdriver, size 5.5 mm Needed when removing the Communicator from DIN-rail. • Flat-head screwdriver, size 3 mm Needed when connecting the cables to the 7-pin connector. Page 4 of 28 SP2980 1.
Support and Resources Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial 3.3. Support and Resources For additional documentation and software downloads, FAQs, troubleshooting guides and technical support, please scan the QR code to visit the Communicator support web page. You can also visit www.anybus.com/support and enter the product article number to search for the Communicator support web page. You find the product article number on the product cover. SP2980 1.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Installation 4. Installation 4.1. DIN Rail Mounting IMPORTANT The equipment must be electrically grounded through the DIN rail for EMC compliance. Make sure that the equipment is correctly mounted on the rail and that the rail is properly grounded. Figure 1. Attach the Communicator on the DIN rail Page 6 of 28 SP2980 1.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Connect to PROFIBUS Network 4.2. Connect to PROFIBUS Network Figure 2. Connect to PROFIBUS network PROFIBUS Connector SP2980 1.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Connect to Serial RS232/RS485 Subnetwork 4.3. Connect to Serial RS232/RS485 Subnetwork NOTE Use minimum 90 oC copper (Cu) wire only. Figure 3. Connect to serial RS232/RS485 subnetwork Page 8 of 28 SP2980 1.
Connect to Serial RS232/RS485 Subnetwork 7-pin connector SP2980 1.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Rotary Switch Settings 4.4. Rotary Switch Settings 4.4.1. Rotary Switches Default Setting By default, the value on the three rotary switches are set to 000. Figure 4. Rotary switches default setting 000. Page 10 of 28 SP2980 1.
Rotary Switch Settings Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial 4.4.2. Set a Node Address with Rotary Switches About the Rotary Switch Settings To set a node address for the PROFIBUS server, use the rotary switches located on the top front of the Communicator . TIP Use Windows Calculator (or similar application) to convert between hexadecimal (hex) and decimal (dec). • The default node address setting is 000.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Rotary Switch Settings Before You Begin Ensure that the Communicator is disconnected from power. Figure 5. Disconnect Communicator from power Procedure Use a screwdriver to change the rotary switch position. Ensure that the rotary switches engage correctly. Page 12 of 28 SP2980 1.
Rotary Switch Settings Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Example 1. To set the node address 12 hex = 18 dec 1. The rear rotary switch A is not used, ensure that it is set to 0. 2. Set the center rotary switch B to 1 hex. 3. Set the front rotary switch C to 2 hex. The center rotary switch B 1 hex = 1 dec and the front rotary switch C 2 hex = 2 dec. The node address expressed in decimal numbers is therefore 16 x 1 + 2 = 18. SP2980 1.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Rotary Switch Settings Example 2. To set the node address 7E hex = 126 dec • The rear rotary switch A is not used, ensure that it is set to 0. • Set the center rotary switch B to 7. • Set the front rotary switch C to E. The center rotary switch B 7 hex = 7 dec and the front rotary switch C E hex = 14 dec. The node address expressed in decimal numbers is therefore 16 x 7 + 14 = 126. Page 14 of 28 SP2980 1.
Rotary Switch Settings Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial To Do Next Connect the Communicator to power. See Connect to Power (page 16). Figure 6. Connect Communicator to power Result The set node address is active as soon as the Communicator is powered on. NOTE Changing the address settings on the rotary switches during operation is ignored. For a new address to take effect, power cycle the Communicator . SP2980 1.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Connect to Power 4.5. Connect to Power CAUTION Ensure that the power supply is turned off before connecting it to the equipment. IMPORTANT Using the wrong type of power supply can damage the equipment. Ensure that the power supply is connected properly and of the recommended type. IMPORTANT Before you connect the Communicator to power, ensure that the PROFIBUS address is set on the rotary switches.
Connect to Power Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Figure 7. Connect to power Power port SP2980 1.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Security Switch 4.6. Security Switch NOTE After completing the configuration of the Communicator, lock the security switch to prevent unauthorized access to the Communicator built-in web interface. When the security switch is in its locked position, the Communicator built-in web interface can not be accessed and the Communicator can not be configured using the built-in web interface.
Security Switch Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Security Switch Status LED Figure 9. Security switch locked status LED When the security switch is in its: • locked position, the security switch status LED turn solid green. • unlocked position, the security switch status LED is turned off. SP2980 1.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Lock the Cables 4.7. Lock the Cables Figure 10. Lock the cables To strain relieve the cables, place a cable tie in the holder and lock the cables. Page 20 of 28 SP2980 1.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial DIN Rail Demount 4.8. DIN Rail Demount Before You Begin IMPORTANT Be careful when removing the Communicator from the DIN-rail. If not removed properly, the DIN rail locking mechanism and the product cover can break. Have a flat-blade screwdriver, size 5.5 mm, available. Procedure Remove the Communicator from the DIN Rail: 1. Insert the screwdriver into the Communicator DIN rail locking mechanism. 2.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial DIN Rail Demount 3. Hold the screwdriver in the DIN rail locking mechanism while you unhook the Communicator from the DIN rail. Figure 12. Unhook the Communicator Page 22 of 28 SP2980 1.
Configuration Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial 5. Configuration 5.1. Connect to PC and Power Figure 13. Connect to PC and Power 1. 2. Connect an Ethernet cable between the Communicator configuration port and your PC. Connect the Communicator to a power supply. SP2980 1.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Find the Communicator on Your PC 5.2. Find the Communicator on Your PC The Communicator default IP address is 192.168.0.10. To be able to access the Communicator built-in web interface. Option 1| Set a static IP address on the PC On the PC accessing the Communicator built-in web interface, set a static IP address within the same IP address range as the Communicator IP address.
Configure the Communicator Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial 5.3. Configure the Communicator Figure 14. The Communicator built-in web interface Home page Open the Communicator built-in web interface in HMS IPconfig or enter the Communicator IP address in your web browser. The built-in web interface takes you through the steps to configure the Communicator. Support and Resources If you need more in-depth information about the configuration, please visit www.anybus.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Technical Data 6. Technical Data For complete technical specifications and regulatory compliance information, please visit www.anybus.com/support. 6.1.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Communicator LED Indicators 7. Communicator LED Indicators NOTE Before you can verify operation you must configure the Communicator. Figure 15.
Anybus® Communicator™ - PROFIBUS to Modbus RTU/Serial Communicator LED Indicators LED A LED B LED C LED D Operation Status Gateway status PROFIBUS Subnetwork Security switch Green Operational Operate, data exchange Running Security switch is locked Red Exception/Fatal error FATAL event Fatal error N/A Red, one flash Exception/Fatal error Parameterization error Fatal error N/A Red, two flash Exception/Fatal error PROFIBUS configuration error Fatal error N/A Green/Red, flashing