98 (124)
Create Write Parameter (0x02)
The Communicator writes values delivered from the PLC to the My Drive node.
1. Add an Empty template and select it.
2. Name the template Write parameter (0x02).
3. In the Frame editor Request area, add six frame fields with the following settings:
Request frame fields
Frame field
Name
Bytes/Length Type/
Checksum type
Endianess Fixed field Value (Hex)
Constant
Function code
1 Byte
N/A
Yes
N/A
Node address Node ID
1 Byte
N/A N/A N/A
Constant
Index
2
Word (two
bytes)
Big-endian
No Min 0
Max 1000
Constant
Sub index
1 Byte
N/A
No Min 0
Max 255
Data Data 2 Byte
N/A
Yes
N/A
Checksum Checksum
2 CRC
N/A N/A N/A
4. In the Frame editor Response area, add five frame fields with the following settings:
Response frame fields
Frame fields
Name Bytes
Type/
Checksum type
Endianess Fixed field Value (Hex)
Constant
Function code
1 Byte
N/A
Yes
N/A
Node address Node ID
1 Byte
N/A N/A N/A
Constant
Index
2
Word (two
bytes)
N/A
No Min 0
Max 1000
Constant
Sub index
1 Byte
N/A
No Min 0
Max 255
Checksum Checksum
2 CRC
N/A N/A N/A
Anybus
®
Communicator
User Manual
SCM-1202-176 1.0 en-US