Instructions

Table Of Contents
Communicator Configuration 65 (124)
5. Configure the Transaction settings.
Setting Value Description
Transaction
name
N/A
You can name the transaction to make it easier to identify.
Read quantity
1 to 125
Specifies the number of registers to read in the read data field.
Appear when Modbus transaction Read Write Multiple Registers
(23) is selected.
Address
0 to 65 535
Specify the start address for the read/write transaction.
The address acts as an address to the data position, where the
data is read from or written to.
Modbus holding register addresses starts at 0.
Modbus address 0 = Register 1
Write quantity
Read Write Multiple
Registers (23)
1 to 123
Specifies the quantity of registers/coils to write in the write data
field.
Appear when Modbus transaction Read Write Multiple Registers
(23) is selected.
Quantity
Read Holding Registers (3)
Read Input Registers (4)
1 to 125
Write Multiple Coils (15)
1 to 1968
Write Multiple Registers
(16)
1 to 123
Read Coils (1)
Read Discrete Inputs (2)
1 to 2000
The Quantity parameter appear when you select a Modbus
transaction that can address more than one data object.
Example when Quantity is set: For the Modbus Transaction Read
Input Registers (4) you need to set the Quantity in order to define
the array of data.
Example when no Quantity is set: For the Modbus Transaction
Write Single Coil (5) you do not need to set the Quantity
parameter because there can not be an array of data. The
transaction is used to write a single output to either ON or OFF in
a remote device.
For Write Single Coil (5), Write Single Register (6) and Mask Write
Register (22) Quantity cannot be set.
Constant 0 to 255
The value of the Constant in the frame.
Data 0 to 512
The length of the data field.
Variable data
0 to 255
The maximum payload length of the variable data field.
Update mode Cyclically
On data change
Single shot
Change of state on trigger
Specify when a transaction shall be sent to the server.
The transaction is issued cyclically, at the interval specified in the
Update time parameter.
Cyclically: The transaction is sent cyclically, at the interval
specified in the Update time parameter.
On data change: The transaction is sent when the data is changed.
Single shot: The transaction is issued once at start up.
Change of state on trigger: The transaction is triggered when the
content of a specified byte changes. In the I/O data map, the
node will be marked with a flash icon.In the I/O data map you can
also configure the area map and the trigger byte address. Refer to
Trigger Byte, p. 74.
Update time
3 ms to 60 000 ms
Update mode parameter must be set to Cyclically. The Update
time parameter appear when Cyclically is select.
Specify how often, in steps of 10 ms, the transaction are going to
be issued.
Positive ack
N/A
When Positive Acknowledgement is enabled, the positive ack data
byte in the I/O data map is incremented each time this
transaction succeeds.
Negative ack
N/A
When Negative Acknowledgement is enabled, the negative ack
data byte in the I/O data map is incremented each time this
transaction fails.
6. To apply the settings, click Apply in the web-interface header, and follow the instructions..
Anybus
®
Communicator
User Manual
SCM-1202-176 1.0 en-US