Configure the actual temperature transaction:
5. To add a second transaction, click Add.
6. Select the transaction to configure.
7. In the transaction sidebar, on the right side of the screen.
Enter values for the transaction settings.
Actual temperature transaction settings:
Setting
Value
Description
Transactio
name
Actual Temp Give the transaction a name.
Modbus
transaction
Read Holding
Registers (3)
This register read the actual temperature from the temperature regulator to the
PLC.
Address Address: 0
Register: 1
Address 0 is Register 1.
Quantity 1
The transaction will address one data object.
Update
mode
Cyclically Default value, can not be changed.
Update time
1000 ms
The update cycle is 1000 ms.