10.1.6. Setup the Transacons
Set up the communicaon between the node and the master.
In this example, the communicaon between the Temperature Regulator and the PLC.
The Temperature Regulator has two Modbus transacons:
One registers holding the setpoint temperature.
One registers holding the actual temperature.
Congure the temperature setpoint transacon
Figure 89. Temperature setpoint transacon
1. Select the Temp Regulator node.
2. To add a transacon, click Add.
3. Select the transacon to congure.
4. In the transacon sidebar, on the right side of the screen.
Enter values for the transacon sengs.
Table 2. Setpoint temperature transacon sengs
Seng Value Descripon
Transacon name Temp Setpoint Give the transacon a name.
Modbus transacon Write Mulple Registers
(16)
The PLC writes a block of conguous registers to the temperature regulator.
Address/ Register Address: 0
Register: 1
Address 0 is Register 1.
Quanty 1 The transacon will address one data object.
Update mode Cyclically The temperature regulator sends a new message cyclically, every 1000 ms.
Update me 1000 ms The update cycle is 1000 ms.
Temperature Regulator - Modbus RTU Use Case Anybus
®
Communicator
- EtherNet/IP
to Modbus RTU/Serial