Manual

Table Of Contents
Congure the actual temperature transacon
Figure 90. Actual temperature transacon
1. To add a second transacon, click Add.
2. Select the transacon to congure.
3. In the transacon sidebar, on the right side of the screen.
Enter values for the transacon sengs.
Table 3. Actual temperature transacon sengs:
Seng Value Descripon
Transaco name Actual Temp Give the transacon a name.
Modbus transacon Read Holding Registers
(3)
This register read the actual temperature from the temperature regulator to the
PLC.
Address Address: 0
Register: 1
Address 0 is Register 1.
Quanty 1 The transacon will address one data object.
Update mode Cyclically Default value, can not be changed.
Update me 1000 ms The update cycle is 1000 ms.
Anybus
®
Communicator
- EtherNet/IP
to Modbus RTU/Serial Temperature Regulator - Modbus RTU Use Case
Page 100 of 133 SCM-1202-152 Version 1.12