Manual
Table Of Contents
- Anybus® Communicator™ - EtherNet/IP™ to Modbus RTU/Serial
- Table of Contents
- 1. Preface
- 2. Safety
- 3. Preparation
- 4. About Anybus Communicator
- 5. Installation
- 6. Configuration Quick Guide
- 7. Communicator Configuration
- 7.1. Connect the Communicator
- 7.2. Access the Built-In Web Interface From HMS IPconfig
- 7.3. Access the Built-In Web Interface From a Web Browser
- 7.4. Communicator Built-In Web Interface Overview
- 7.5. General Subnetwork Settings
- 7.6. About Transaction Templates
- 7.7. Build Transaction Template
- 7.8. Nodes and Transactions
- 7.9. High Level Network Settings
- 7.10. I/O Data Map
- 7.11. Configuration Notes
- 7.12. Apply Configuration
- 7.13. To Use an Existing Configuration
- 7.14. To Use an Communicator Classic Configuration
- 8. PLC Configuration
- 9. Verify Operation
- 10. Use Cases
- 11. Maintenance
- 12. Troubleshooting
- 13. Technical Data
- 14. Reference Guides
Congure the actual temperature transacon
Figure 90. Actual temperature transacon
1. To add a second transacon, click Add.
2. Select the transacon to congure.
3. In the transacon sidebar, on the right side of the screen.
Enter values for the transacon sengs.
Table 3. Actual temperature transacon sengs:
Seng Value Descripon
Transaco name Actual Temp Give the transacon a name.
Modbus transacon Read Holding Registers
(3)
This register read the actual temperature from the temperature regulator to the
PLC.
Address Address: 0
Register: 1
Address 0 is Register 1.
Quanty 1 The transacon will address one data object.
Update mode Cyclically Default value, can not be changed.
Update me 1000 ms The update cycle is 1000 ms.
Anybus
®
Communicator
™
- EtherNet/IP
™
to Modbus RTU/Serial Temperature Regulator - Modbus RTU Use Case
Page 100 of 133 SCM-1202-152 Version 1.12










