7.10.1. Opmize the I/O Data Map
The opmize funcon is used to automacally remove gaps between the mapping.
IMPORTANT
Opmize remove gaps between the data objects in the map and should be used with care on already
commissioned systems. Expected mapping in the PLC may change.
NOTE
If you opmize the I/O data map, the current I/O data map will be overwrien.
Figure 61. I/O data map page, Opmize
To opmize the map:
1. Click Opmize.
2. To conrm, click OK.
I/O Data Map Anybus
®
Communicator
™
- EtherNet/IP
™
to Modbus RTU/Serial
SCM-1202-152 Version 1.12 Page 75 of 133