How to Enable Trigger Byte on a Node
Procedure
1. Navigate to the Nodes & transacons page.
2. Select the decried node and transacon.
3. In the transacon sidebar Update mode menu, select Change of state on trigger.
4. Navigate to the I/O data map page.
5. The transacon with the trigger byte enabled is marked with a ash icon.
To open the Map Area sidebar, click on the ash icon.
6. In the Map Area sidebar, specify the map area to use and the trigger byte address:
Map area opons
From EtherNet/IP: The trigger byte is stored in the I/O data map Data from EtherNet/IP area.
General: The trigger byte is stored in the I/O data map General area.
Unmapped: The transacon data is not used.
Address
Enter an Address, the locaon in the specied Map area (From EtherNet/IP or General) where the trigger
byte will be saved.
Value: 0 (default) to 1499
7.10.5. Endian Swap
By default EtherNet/IP uses the lile-endian format.
Big-endian
The big-endian format places the most signicant byte of the data at the byte with the lowest memory address.
Lile-endian
The lile-endian format places the least signicant byte of the data at the byte with the lowest memory address.