Datasheet

POWER
ETHERNET PORTS
EtherCAT MainDevice
PROFIBUS
Input voltage 12 - 30 VDC
Current consumption Typical: 160 mA @ 24V Max: 400 mA @ 12V
Power connector 3-pin plug with screw terminal
Protection Reverse voltage protection and short circuit protection
Ports 2 x Ethernet ports per Ethernet protocol
Isolation Galvanic isolation
Bitrate 10/100 Mbit full duplex
Connector RJ45
Switch. Dual port cut-through switch
Mode MainDevice
Cycle times supported 1, 2 ,4, 8, 16, 32, 64, 128 ms
Max number of SubDevices 24
Input data size 1500 bytes
Output data size 1500 bytes
Data transfer Cyclical data transfer with PDOs (SDOs are not supported)
SubDevice discovery Scan to discover SubDevices via a web user interface (ESI files are not supported)
SubDevice PDOs Default data is mapped to the control system (can’t pick what to map)
Mode PROFIBUS DPV1 Device (slave)
Input data size 244 bytes
Output data size 244 bytes
Baude rate Automatic baud rate detection up to 12 Mbit/s
Rotary switches PROFIBUS slave address setting via onboard rotary switches or web interface
Features Supports Sync and Freeze and Watchdog
I&M records Manufacturer data (I&M0), Tag information (I&M1), Date/Time (I&M2), Description (I&M3)
Connector 1x D-sub 9-pin female PROFIBUS connector