Figure 4-2 Status Display Screen
4 Control module
  User’s Information Manual
OPERATION DISPLAY
1.  Once the gas pressure switch(es) are closed, the control turns 
on the appropriate pumps (system and boiler pumps for space 
heating, DHW pump for DHW). The flow switch and/or LWCO 
must close.
Upon a call for heat, the control turns on the appropriate pumps.  
The flow switch and/or LWCO must close. Once the LWCO has 
closed, the auxiliary limit switch must close.
2. The control turns on power to the louver relay. The louver 
proving switch, and blocked drain switch must close.
3.  The control starts the prepurge cycle by initiating the blower.
4.  The control starts the trial for ignition by firing the spark 
  electrode and opening the gas valve.
5.  If flame is not detected after the sparking ends, the control will 
 perform a postpurge, then start another prepurge cycle and try 
 to light the burner again. The control will perform a total of 4 
 attempts before locking out.