Install Instructions
4 Control module (continued)
13
  User’s Information Manual
OPERATION DISPLAY
6.  If flame is detected, it holds the firing rate steady for a few 
seconds to let the flame stabilize, then it begins to modulate the 
firing rate based on a set point or some other command.
7. If the space heating call for heat is active and the combi flow 
switch starts a DHW call for heat, the diverter valve will move to 
the DHW position and the boiler will switch to the DHW Mode.  
This will divert the boiler's outlet water from the heating system to 
the brazed plate heat exchanger. The control will then modulate 
to maintain the DHW outlet temperature at the DHW set point.
8.  Once all calls for heat are satisfied, the control will turn off   
 the burner. The blower will continue to run during the postpurge 
 period.
9.  Any pumps that are running will continue to run for their 
respective pump delay times before turning off. A 60 second 
anti-cycle period will start, which will delay any new space 
heating call for heat until it times out.
10.  In Standby, ready to start a new cycle.
ProLine® XE 
Combi Boiler