Install Instructions
Table Of Contents
- Safe Installation, Use and Service
- APPROVALS
- General Safety Information
- Introduction
- Features And Components
- Installation Considerations
- Installation Requirements
- Gas Supply Systems
- Supply Gas Regulator
- Power Supply
- Mixing Valves
- Dishwashing Machines
- Closed Water Systems
- Thermal Expansion
- Temperature-Pressure Relief Valve
- Condensate Drain
- Combustible Material Storage
- Contaminated Air
- Air Requirements
- Unconfined Space
- Confined Space
- Fresh Air Openings For Confined Spaces
- Outdoor Air Through Two Openings
- Outdoor Air Through One Opening
- Outdoor Air Through Two Horizontal Ducts
- Outdoor Air Through Two Vertical Ducts
- Air From Other Indoor Spaces
- Installation Requirements - Commonwealth of Massachusetts
- Venting Installation
- General Venting Information
- General Venting Instructions
- Intake Air Connection
- Venting Requirements
- Venting Installation Sequence
- Power Vent Installation
- Direct Vent Installation
- Vertical Termination Installation
- Sidewall Termination Installation
- Polypropylene Installations
- Al29-4C® Vent Installations
- Concentric Termination Installation
- 4 Inch Concentric Termination Installation
- Low Profile Vent installation
- Venting Arrangements
- Termination Clearances Sidewall Power Vent
- Termination Clearances Sidewall Direct Vent
- Water Heater Installation
- Temperature Regulation
- Control System Operation
- Start Up
- Troubleshooting
- Maintenance
- Diagrams
- notes
- notes
- notes
- Service Inquiries:
- Commercial
- Water Heater
- Limited Warranty
55
with other gas red appliances; the supply gas pressures shall
be measured at each water heater with all gas red appliances
connected to a common main ring at full capacity.
On multiple water heater installations the supply gas line
regulators shall be adjusted to provide gas pressure to each
water heater within the minimum and maximum supply pressure
requirements listed in Table 3 on page 11 with all gas red
appliances connected to a common gas main ring at full capacity.
NOTE: A pressure drop of more than 1.5” W. C. (0.37 kPa) when
the Main Burner ignites is an indication of an inadequate supply
of gas and can lead to ignition failure, rough starts and/or rough
operation. If a drop of more than 1.5” W. C. (0.37 kPa) in supply
gas pressure occurs when the Main Burner ignites, ensure the
supply gas lines and regulator(s) are properly sized and installed.
See the requirements for Supply Gas Regulator and Gas Supply
Systems on page 13. See Supply Gas Line Installation on
page 40 and Supply Gas Regulator on page 13. Ensure all
requirements and installation instructions are maintained.
MANIFOLD GAS PRESSURE
The manifold pressure is non adjustable. The manifold gas
pressure is factory set and cannot be eld adjusted. If the
manifold gas pressure readings taken on these models is off by
more than ± 0.3" W. C. from the listed values in Table 3 on page
11 call the technical support phone number listed on the back
cover of this manual for further assistance.
SUPPLY GAS PRESSURE ADJUSTMENT
Fire and Explosion Hazard
Turn off gas lines during installation.
Contact a qualified installer or service
agency for installation and service.
Excessive gas pressure to gas valve can
cause serious injury or death.
Do not use water heater with any gas
other than the gas shown on the rating
label.
Supply gas pressure shall be measured while the water heater is
not ring (static pressure) AND while the water heater is ring at
full capacity (dynamic pressure).
If the supply gas pressure to the water heater is not between the
required minimum and maximum values given in Table 3 on page
11 adjust the supply gas regulator as necessary. Adjust the supply
gas regulator(s) per the regulator manufacturer’s instructions to
achieve the required “static” and “dynamic” supply gas pressure.
Multiple Water Heater Installations:
In multiple water heater installations or in installations where
the installed water heater(s) share a common gas supply main