FAULT AND ALERT MESSAGES
Call the technical support phone number listed on the back cover for further technical assistance or to locate a qualied service agent
in your area.
POSSIBLE CAUSES - CHECK/REPAIR DISPLAYED FAULT/ALERT MESSAGE
Using a manometer, ensure that gas supply pressure is above
minimum requirement listed on heater’s data plate and does not
drop more than 1.5” W.C. when unit res.
Ensure wire connections to gas valve are clean and tight.
Ensure wire connections to ame sensor are clean and tight.
Ensure wire connections to spark igniter are clean and tight.
Inspect ame sensor, clean/replace as needed.
Inspect spark igniter, realign igniter gap as needed
Ensure adequate electrical ground to heater.
CHANGE BACK
ADVANCED
Ignition Failure
Fault occurred 2 mins ago
Flame not detected. Clean flame rod.
Check gas supply.
Call a service professional:
Your Company Name Here
(press [DOWN] for more....)
Conrm supply gas is turned on.
Using a manometer, ensure the supply gas pressure is above
minimum pressure requirement listed on heater’s data plate
before and during operation.
Ensure wire connections to gas pressure switch are clean and
tight.
If all above conditions are met, replace gas pressure switch.
CHANGE BACK
ADVANCED
Low Gas Pressure
Fault occurred 2 mins ago
Gas pressure is below minimum
required to operate this unit. Check
gas pressure and switch.
Call a service professional:
Your Company Name Here
(press [DOWN] for more....)
If Blocked Exhaust error occurs when blower is running, check for
restrictions in exhaust pipe, including exhaust elbow, condensate
drain, and outside termination. Also check exhaust pipe installation
(size/length) per manual.
If Blocked Exhaust error occurs before blower runs, make sure
pressure switch connections are clean and tight. Check pressure
switch continuity/resistance. Switch should be closed (continuity/0
ohms). Replace switch if open (no continuity).
Other possible causes: high wind conditions and excessive
negative air pressure in building.
CHANGE BACK
ADVANCED
Blocked Exhaust
Fault occurred 2 mins ago
Restriction in exhaust pipe. Check
exhaust pipe and termination for
blockage.
Call a service professional:
Your Company Name Here
(press [DOWN] for more....)