Install Instructions

32 www.hotwater.com
Calculating Equivalent Feet
WATER
HEATER
MODEL
HEATER
INPUT
(Btu/hr)
VENT SIZE
(Inside
Diam)
PRESSURE
SWITCH
SETTING
MAXIMUM EQUIVALENT
VENT LENGTH
MINIMUM EQUIVALENT
VENT LENGTH
40 & 50 gal. 40,000
2” (50mm)
- 0.27 in. w.c.
50 ft. (15.2m) +
termination elbow
7 ft. (2.1m) +
termination elbow
60 gal. 42,000 - 0.27 in. w.c.
40 & 50 gal. 50,000 - 0.37 in. w.c
40 & 50 gal. 40,000
3” (76mm)
- 0.27 in. w.c.
125 ft. (38.1m) +
termination elbow
7 ft. (2.1m) +
termination elbow
60 gal. 42,000 - 0.27 in. w.c.
40 & 50 gal. 50,000 - 0.37 in. w.c.
50 gal. (short) 62,000
3” (76mm)
- 0.99 in. w.c.
50 ft. (15.2m) +
termination elbow
7 ft. (2.1m) +
termination elbow
50 gal. (tall) 65,000 - 0.99 in. w.c.
75 gal. 72,000 - 0.99 in. w.c.
40 & 50 gal. 40,000
4” (102mm)
- 0.27 in. w.c.
180 ft. (54.9m) +
termination elbow
125 ft. (38.1m) +
termination elbow
60 gal. 42,000 - 0.27 in. w.c.
40 & 50 gal. 50,000 - 0.37 in. w.c.
50 gal. (short) 62,000
4” (102mm)
- 0.99 in. w.c.
125 ft. (38.1m) +
termination elbow
50 ft. (15.2m) +
termination elbow
50 gal. (tall) 65,000 - 0.99 in. w.c.
75 gal. 72,000 - 0.99 in. w.c.
Equivalent lengths of straight pipe for various elbows using Schedule 40 PVC, CPVC and polypropylene.
Size Type
Short Sweep/
Short Radius
Long Sweep/
Long Radius
Notes:
1. Use long radius elbows where
possible. Minimum distance between
90º elbows should be 6” (150mm)
wherever possible.
2. Venting systems may use a maximum
of ve (5) 90° elbows.
3. Use proper screen termination (see
Figures 32 & 33).
2” (50mm)
3" (76mm)
4" (102mm)
90° elbow 8 ft. (2.44m) 5 ft. (1.52m)
2” (50mm)
3" (76mm)
4" (102mm)
45° elbow 4 ft. (1.22m) 2.5 ft. (0.76m)
Table 2
Example for calculating equivalent feet.
Section “A” 0.5 ft. (0.15m)
90° elbow 8.0 ft. (2.44m)
Section B 1.0 ft. (0.31m)
45° elbow 4.0 ft. (1.22m)
Section C 1.5 ft. (0.46m)
45° elbow 4.0 ft. (1.22m)
Section D 15.0 ft. (4.57m)
Total Equivalent 34.0 ft. (10.37m)
Based on this example use the (fully open) rodent
screen for vent length greater than 20 equivalent ft.
(6.1 equivalent metres) (see Figures 32 & 33).
Note: The vent pipe must be supported every 4 ft. (1.2M). To prevent vibration and sagging, it is recommended
to use isolation pads when attaching straps to oor joists, walls or ceilings. PVC and CPVC vent pipe should be
sloped upwards away from the blower assembly at a pitch of 1/8 in. (3mm) rise per 4 ft. (1.2M). Polypropylene
vent systems require a 1/4” (6mm) per 1 ft. (0.3M) upward slope to ensure proper drainage.
STRAP
45° SHORT
ELBOW
90° SHORT
ELBOW
RODENT
SCREEN
(INSTALL INTO
ELBOW)
TERMINATION
ELBOW
GROUND LEVEL
12” (305mm) MIN. OR
ABOVE ANTICIPATED
SNOW LEVEL.
COVER PLATE
(OPTIONAL)
Figure 34