Page 23 of 104 Report No.: HK2107050725-SR
UL 507
Clause Requirement + Test Result - Remark Verdict
TRF No. UL507A
16.6 The overcurrent protection shall be connected to
the ungrounded conductor of the power supply.
P
17 Special Protection Devices N/A
17.1 Ground-fault circuit-interrupters (GFCI) for
protection against electrical shock shall comply
with the Standard for Ground-Fault Circuit-
Interrupters, UL 943. The following statement, or
equivalent, shall be included as a marking near the
GFCI, or as an instruction in the manual: Press
the TEST button (then RESET button) every month
to assure proper operation.
N/A
17.2 Note An ALCI is not considered an acceptable
substitute for a GFCI when the National Electrical
Code, ANSI/NFPA 70, requires a GFCI.
N/A
17.3 Equipment ground-fault protective devices shall
comply with the Standard for Ground-Fault Sensing
and Relaying Equipment, UL 1053, and the
applicable requirements of the Standard for
Ground-Fault Circuit-Interrupters, UL 943.
N/A
17.5 The AFCI or LCDI shall be installed as an integral
part of the attachment plug or located in the supply
cord within 102 mm (4 inches) of the attachment
plug.
N/A
17.6 Arc fault detection testing shall include the
following, as applicable:
a)Carbonized path arc clearing time test;
b)Point contact arc test;
c)Unwanted tripping test Load Condition I;
d)Unwanted tripping test Load Condition II
Condition C and D;
e)Unwanted tripping test Load Condition III
Condition A; and
f)Masking.
N/A
17.7 An AFCI or LCDI provided as part of an appliance
intended for outdoor use shall comply with the
applicable requirements of Sections 165 167.
N/A
18 Live Parts P