Specifications
Document No. DER05105  TROUBLESHOOTING 
Page 8 of 16  Effective Date  15 Jul 08 
Alarm and Fault Messages 
Cause  Corrective Action 
Conveyor VFD Ground Warn Alarm, Ref Troubleshooting Section of User Manual 
Conveyor motor has path to ground  Check for ground in conveyor motor and connections 
to drive output, and correct defect. 
Conveyor VFD In Phase Loss Alarm, Ref Troubleshooting Section of User Manual 
Check wiring between VFD and motor; correct 
defect(s). 
Ground detected between VFD and 
motor in one phase 
Check motor winding for grounded phase; remove 
ground, if any. 
Conveyor VFD Power Loss Alarm, Ref Troubleshooting Section of User Manual 
Incoming power loss or low voltage 
supply 
Monitor and correct incoming power defect(s). 
Conveyor VFD Undervoltage Alarm, Ref Troubleshooting Section of User Manual 
Incoming power loss or low voltage 
supply 
Monitor and correct incoming power defect(s). 
Electrical Enclosure High Temperature Alarm 
Check that air conditioner is operative; repair or 
replace air conditioner, if defective. 
Reduce load by decreasing bowl, conveyor 
differential speed, and/or pump feed rate. 
PLC has detected high temperature 
inside control cabinet 
Check VFD temperatures (refer to DER04098
); 
replace VFD if defective. 
Electrical Enclosure High Temperature Fault and Shutdown 
Check that air conditioner is operative; repair or 
replace air conditioner, if defective. 
Reduce load by decreasing bowl, conveyor 
differential speed, and/or pump feed rate. 
PLC has shut down centrifuge due to 
high temperature inside control cabinet 
Check VFD temperatures (refer to DER04098
); 
replace VFD if defective. 
Interior temperature of control cabinet 
too high, causing shutdown 
Check that air conditioner is operating; repair or 
replace, as indicated. Inspect cabinet interior, and 
remove cause of high temperature, if any. 
Re-start centrifuge after removing cause of high 
temperature. 










