Specifications
OPERATING INSTRUCTIONS Document No. DER04098 
Effective Date  06 Jun 08  Page 19 of 19 
Excessive Vibration 
Excessive vibration of the centrifuge will cause the vibration switch to interrupt electric power to 
the centrifuge run relay, shutting down the machine. Such excessive vibration may occur during 
startup or normal operation due to slumping of the wall cake or other unbalanced condition of the 
bowl. The machine may be re-started by pressing the reset button on the vibration switch and 
then using the Normal Startup procedure above. 
If nuisance tripping occurs during normal startup, the reset button may be held depressed until full 
speed is reached. 
Main Bearing Temperatures 
Temperature sensors are installed on the liquid and solid end main bearings and connected to the 
PLC. Bearing temperatures are continuously displayed on the Operation screen. An alarm 
message is displayed on the control panel when bearing temperature exceeds 225°F (107°C). If 
temperature rises to 250°F (120°C), a fault message appears and the centrifuge is shut down. 
Excessively high bearing temperatures usually indicate bearing failure, which can result from 
inadequate lubrication, contamination, or normal wear. Refer to 
DER05024 for main bearing 
replacement procedure. 
Note: Both main bearings should be replaced if centrifuge has shut down due 
to high main bearing temperature. 
Excessive Bowl Speed 
A sensor that detects the rotating speed of the bowl provides an input to the PLC that produces a 
continuous display of actual bowl speed on the Operation and VFD screens. If the bowl speed 
exceeds 3050 RPM, the bowl speed sensor provides an input to the PLC causing an alarm 
message to be displayed on the control panel. A fault message is displayed and the centrifuge is 
immediately shut down if speed rises to 3100 RPM. To re-start the centrifuge, allow the bowl to 
coast to a complete stop, check for and remove the cause of excessive speed. With bowl at a 
complete stop, check speed sensor as follows: 
1.  Check speed sensor connections. 
2.  With bowl at a complete stop, check for a zero bowl speed reading on bowl VFD screen 
(Figure 4098-10). A reading of “0” indicates no defects in sensor and connection. If reading is 
greater than 3250 RPM, check sensor and/or connection. 
3.  Replace sensor if defective, and/or repair damaged connection. 
4.  After correcting any defect(s), re-start the machine using the Normal Startup procedure above, 
and re-check bowl speed. 
The content of this document is subject to change at any time. Information provided does not cover all details or variations possible 
with DERRICK equipment; nor does it cover every contingency that may be met during installation, operation, maintenance, or 
troubleshooting of the equipment. If additional information is required, or should situations arise that are not covered by this manual, 
bring the matter to the attention of your local DERRICK representative or the Service Department at DERRICK Corporation in 
Buffalo, New York. 
Copyright© 2007 by DERRICK CORPORATION 










