Instruction manual
KRB-5377
106
1
Repeat steps 1 to 5 for the wire on the
other end of the cable.
Temporarily tighten the cable
fixing nut.
Holding the wire, tighten the
Wire fixing nut to a torque of
4.7 to 5.9 N.m.
Push in and hold the wire until
It sto
p
s a
g
ainst the
g
roove end
Loosen the cable fixing nut and the wire fixing nut.
A
ttach the cable in the cable mounting
Hole and insert the wire into the wire
Insertion hole of the wire fixing bolt.
6
Make sure the distance between the support and the lever is
as specfied and then tighten the cable fixing nut to a torque
of 12.5N.m. If the distance is out of the specfied range,
proceed to step 8 to adjust the distance.
3
5
4
7
If the ACBs are of a draw-out type, insert the ACB bodies into the
chassis to the connected position. Do not turn the ACB(s) on
until it is in the connected position. If the ACB is a fixed typed,
unlock the ACB.
A
fter making sure the main circuit is not energised, check the
operation of the ACB(s). Do not touch the interlock during
operation.
8
9
10
Cable
Sleeve
Cable fixing nut
Wire
2
If the distance is too small, turn the cable-fixing nut counter
clockwise to lower the sleeve and the lever, increasing the
distance until it falls within the specified range. If the
distance is too large, turn the cable-fixing nut clockwise to
raise the sleeve and the lever