Instruction manual

KRB-5377
10
Do not install the ACB in such an area that is exposed to direct sunlight.
z Make sure that the mounting base has a sufficient capacity of bearing the weight of the ACB (see Table 3 and Table 4). The
mounting base must be protected against vibration. Take appropriate measures to provide a perfect protection to the mounting
base against resonance. Otherwise, open/close operation of the ACB may cause a malfunction of other devices in the switchboard
or vibrations of the switchboard may cause a malfunction of the ACB.
z Use the following screws with appropriate length for the main circuit terminals.
Main circuit terminal screws: Hex head M10, with flat washers (2), spring washer (1) and nut (1) per screw
Tightening torque: 22.5 - 37.2 N·m
Table 1 Number of main circuit terminal screws required
ACB type AR208S, AR212S, AR216S
AR220S,
AR212H, AR216H, AR220H
AR325S, AR332S
AR316H, AR320H, AR325H, AR332H
AR440SB
AR440S,
AR420H,
AR440H
Vertical terminals 12/16 18/24 24/32 24/32 48/64
Number of main
circuit terminal
screws
(3/4-pole)
Horizontal/front terminals* 12/16 18/24 - -
* Front terminals are not applicable for high-performance ARxxxH types.
z Use the following screw for the ground terminal. The screw must have a length that allows it to be inserted 4 - 9 mm into the
ground terminal M8 tapped hole.
Ground terminal screw: M8 (1) with spring washer and flat washer
Tightening torque: 11.8 - 14.7 N·m