Smart-UPS® VT 10-40kVA 400V Operation Manual
Smart-UPS® VT 10-40kVA 400V Operation Manual ! Output Pwr Zone Probe 10/100Ba Reset se-T AP9619 10/100 Network Managem ent Card EM IMPORTANT! THIS DOCUMENT CONTAINS IMPORTANT SAFETY INSTRUCTIONS – PLEASE SAVE THESE INSTRUCTIONS! Smart-UPS® VT and XR Battery Enclosure 10-40kVA, 400V Operation Manual – 990-1985 1
Contents Safety .....................................................................1 IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . 1 IMPORTANT SAFETY INSTRUCTIONS – SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Symbols used in this guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Environmental symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 General safety symbols . . . . . . . . . . . . . . . . . . . . . .
Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Menu-driven user functions . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Basic display navigation principles . . . . . . . . . . . . . . . . . . . . . . 11 Control functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Status views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Clock set-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Warranty ..............................................................28 LIMITED FACTORY WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . 28 APC product covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Terms of warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Non-transferable warranty extends to first purchaser for use . . 28 Assignment of warranties . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Drawings, descriptions . . . . . .
Safety IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS – SAVE THESE INSTRUCTIONS This guide contains important instructions that should be followed when handling the UPS, Battery Enclosures, and Batteries. Symbols used in this guide WARNING! Risk of electric shock. CAUTION! Read this information to avoid equipment damage. Indicates important information. Note Indicates that more information is available on this subject in a different section of this manual.
Safety – IMPORTANT SAFETY INSTRUCTIONS General safety symbols Two people to lift a component weighing between 18 - 32 kg. For configurations including customer-supplied external batteries, refer to manufacturer’s battery installation and maintenance instructions.
Operation Introduction Welcome to the Operation Manual covering the Smart-UPS® VT. This manual provides you with a detailed description of start-up, operation, and troubleshooting. Separate manuals are available on: • Receiving and Unpacking part no. 990-2284 • Site preparation and Installation part no. 990-2283.
Operation – Introduction Details on the UPS sizes, weight etc. are available in the Appendix under “UPS sizes and weights” on page 36. Note Most illustrations show 523mm Enclosures but apply to both Enclosure sizes. Any differences between the two Enclosure sizes will be addressed in the manual.
The Smart-UPS VT Family Range 352mm Enclosures –10-20kVA ! Output Pwr Zone Probe 10/100BaseT Reset AP9619 10/100 Network Managemen t Card Rear Front EM Front view without front panel Type label 523mm Enclosures – 30-40kVA ! Output Pwr Zone Probe ! Output 10/100Ba Reset Pwr se-T Zone Probe AP9619 10/100Ba Reset 10/100 Network Managem se-T ent Card EM AP9619 10/100 Network Managem ent Card Front 990-2282 Type label Rear EM Front view without front panel Smart-UPS® VT 10-40k
Operation – The Smart-UPS VT Family Range Serial number The serial number is available on the type label placed on the rear side of the UPS. Type label Hotline in US/Canada/LAM: +1 800 800 4APC ¥ Hotline in EMEA: +353 91 70 2000 ¥ Worldwide Support numbers: www.apcc.com/support/contact/ Mark acc. to SKU No. APC SKU SUVT10KH SUVT15KH SUVT20KH SUVT30KH SUVT40KH APC SKU w.
Operation Modes In a stand-alone installation, the UPS has four different operation modes. If the installation includes a Maintenance Bypass Panel test mode will also be available. Normal operation During normal operation, the UPS converts mains power to conditioned power for the connected load. Battery operation During battery operation, the UPS provides power to the connected load from its batteries for a finite period.
Operation – Operation Modes Wrap -around maintenance bypass The UPS can be connected to an external Maintenance Bypass Panel. When activated, this panel bypasses the entire UPS Enclosure (only possible with an optional APC Maintenance Bypass Panel), feeding mains power directly to the load. An activated wrap-around Maintenance Bypass Panel completely isolates the UPS and allows all kinds of maintenance to be performed – including a replacement of the entire UPS.
The Display Introduction CAUTION! The display provides access to more functions than described in this manual. In order to avoid unwanted load impacts these functions should not be accessed without the assistance of APC Customer Support. For APC Worldwide Customer Support, refer to rear cover of this manual. Four Light Emitting Diode (LED) indicators report the operational status of the UPS.
Navigation Menu-driven user functions If you get beyond the functions described in the menu tree, do not proceed. Press ESC to go back.
Operation – Navigation Basic display navigation principles On the display, press ESC until you get to the Overview Screen, which provides you with basic system status information. Press UP, DOWN arrows to navigate with the selector arrow and view all sub-menu screens. Chrg 100% Load 000% 230Vin 000Vout 50Hz Runtime: 0hr 0m Overview Screen Press ENTER to open the Main Menu screen. From here, you command, configure, and monitor the system.
Operation – Navigation Switch load ON. 1. From the Main Menu, select Control and press ENTER 2. Use UP/DOWN key to navigate to Turn Load ON, and press ENTER 3. Select YES, Turn Load ON Switch into bypass. 1. From the Main Menu, select Control and press ENTER 2. Use UP/DOWN key to navigate to UPS into bypass and press ENTER 3. Use UP/DOWN key to navigate to YES, UPS into bypass, and press ENTER Switch out of bypass. 1. From the Main Menu, select Control and press ENTER 2.
Operation – Navigation Load and batteries. Load: Percentage of the load in relation to the total UPS capacity. Bat Voltage: Shows either the positive or negative half of the battery voltage (the lower value of the two will appear). Bat Cap: Percentage charge on the batteries in relation to the total battery capacity. Runtime: The predicted runtime at the current load. Batteries. Bat AmpHr: Battery capacity, including both external and internal batteries.
Operation – Navigation Logging From the logging screen on the Main Menu, you can view the 100 most recent UPS log events, and view the logged details of the events, such as date and time of occurrence, and event number. Control Status Setup Logging Display Diags Help Main Menu 1. From the Main Menu, select Logging 2. Select View Log 3.
Operation – Navigation Alarm threshold If the load level exceeds the preprogrammed threshold, the UPS will display a warning. Example: Alarm Thresholds Load: 20.0 kVA Runtime: 0 hr 0 min Alarm Threshold Screen To change the Alarm Thresholds: 1. Select Setup from the Main Menu 2. Select Alarms from the Setup Menu 3. Press ESC to return to the Main Menu Display setup From the Display Setup screen, you can select your display Language, Contrast, and Beeper functions.
Operation – Navigation From the Beeper Setup Menu, select Beeper Setup. To change the beeper setup, select Beep at and press ENTER. You now have the following options: • Never: If you select this setting, the Beeper will be active at internal UPS errors only. • PwrFail+30: If you select this setting, the Beeper will be active at Internal UPS errors and at mains or bypass errors. The Beeper will only sound if the fault has been present for more than 30 seconds.
Front Panel Removal/Installation Front Panel removal ! Output Pwr Zone Probe 10/100Base-T Reset 10/100 AP9619 Network Management Card EM To remove a Front Panel, turn screw clockwise to unlocked position. Pull top of Front Panel free of UPS. Lift the Front Panel free of the two slots at the bottom of the UPS.
Network Management Card with Environmental Monitor The APC Network Management Card with Environmental Monitor (AP9619) is installed in the UPS as default. It is used for remote system control and monitoring, e-mail notifications, etc. For configuration and use, refer to the separate user manual - Network Management Card with Environmental Monitor - shipped with the UPS.
Display Messages/Troubleshooting This section lists the status and alarm messages that the UPS might display. The messages are listed in alphabetical order, and a suggested corrective action is listed with each alarm message to help you troubleshoot problems. Display messages Display message Meaning Corrective action Automatic Self Test Started. The UPS has started pre-programmed battery test. No corrective action necessary. Batt Temperature Exceeded Upper Limit.
Operation – Display Messages/Troubleshooting 20 Display message Meaning Corrective action Load Is No Longer Above Alarm Threshold. The load previously exceeded the alarm threshold and the situation has been corrected either because the load decreased or the threshold was increased. No corrective action necessary. Load Power Is Above Alarm Limit. The load has exceeded the userspecified load alarm threshold. Option 1: Use the display interface to raise the alarm threshold. Option 2: Reduce the load.
Operation – Display Messages/Troubleshooting Display message Meaning Corrective action Static Bypass Switch Fault. The Static Bypass Switch has failed. Contact APC Customer Support. See rear cover. System Failure Detected by Surveillance. The system has detected an internal error. Check for other alarms and contact APC customer support if problem persists. System Start Up Configuration Failed. System configuration error. Unable to determine system voltage and/or Enclosure size.
Total-Power-Off Procedure WARNING! Risk of electric shock - parts inside the UPS are energized from the battery supply even when the AC power is disconnected. Before electrical installation begins, follow the Total-Power-Off procedure to completely de-energize the system.
Restart procedure Start-up is included with the UPS, and the procedure described here is only applicable if the UPS requires a subsequent start-up. Note Power application WARNING! Only trained personnel familiar with the construction and operation of the equipment may carry out the Start-Up procedure. ON Mains breaker Battery Breaker Box OFF ON OFF UPS ! Output Pwr Zone Probe 10/100Base-T Reset 10/100 AP9619 Network Management Card EM Battery Bank Set the mains breaker to the ON position.
Operation – Restart procedure Wait approximately 30 seconds for the system to boot up and perform a self test. Note After system boot-up, the display will automatically prompt you on how to confirm/select voltage and frequency as shown in the following. Voltage confirmation See display introduction under The Display.
Mechanical Bypass Mechanical Bypass Lever For increased availability, the UPS contains an internal mechanical bypass system providing mains power directly to the output, bypassing all UPS electronics. CAUTION! The load is not protected by the UPS when the internal mechanical bypass system is active and the power is not conditioned. Switch into mechanical bypass If the UPS is running and controllable through the display, carry out steps 1 through 6. If not, go directly to step 4.
Operation – Mechanical Bypass ! Output Pwr Zone Probe 10/100Base-T Reset 10/100 AP9619 Network Management Card ! Output Pwr EM Zone Probe 10/100Base-T Reset 10/100 AP9619 Network Management Card EM Turn the Mechanical Bypass Lever upwards to activate the internal mechanical bypass switch. Reinstall Front Panel. See “Front Panel installation” on page 17. The load will now be supported directly by mains power.
Operation – Mechanical Bypass Switch into normal operation (from mechanical bypass operation) CAUTION! Never attempt to switch the UPS back to normal operation until you have verified that there are no internal UPS faults. Call APC Customer Support (see rear cover of this manual) before switching back to normal operation. If UPS is turned OFF follow steps 1-6. If UPS is running follow steps 4-6. Note Verify the presence of mains supply.
Warranty LIMITED FACTORY WARRANTY The limited warranty provided by American Power Conversion Corporation (“APC”) in this Statement of Limited Factory Warranty applies only to Products you purchase for your commercial or industrial use in the ordinary course of your business. APC product covered Smart-UPS® VT.
Warranty – LIMITED FACTORY WARRANTY Assignment of warranties APC will assign to you any warranties which are made by manufacturers and suppliers of components of the APC Product and which are assignable. Any such warranties are assigned “AS IS” and APC makes no representations as to the effectiveness or extent of such warranties, assumes NO RESPONSIBILITY for any matters which may be warranted by such manufacturers or suppliers and extends no coverage under this Warranty to such components.
Warranty – LIMITED FACTORY WARRANTY SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE, CONSTITUTE SOLE LIABILITY OF APC AND YOUR EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. THE WARRANTIES EXTEND ONLY TO YOU AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
Appendix UPS Components and Options 352mm Enclosures –10-20kVA ! Output Pwr Zone Probe 10/100BaseT Reset AP9619 10/100 Network Managemen t Card Rear Front EM Front view without front panel Type label 523mm Enclosures – 30-40kVA ! Output Pwr Zone Probe ! Output 10/100Ba Reset Pwr se-T Zone Probe AP9619 10/100Ba Reset 10/100 Network Managem se-T ent Card EM AP9619 10/100 Network Managem ent Card Front 990-2282 Type label Rear EM Front view without front panel Smart-UPS® VT
Appendix – UPS Components and Options UPS sizes and weights 32 Height (identical for all Enclosure sizes) 823mm Depth – including Front Panel (identical for all Enclosure sizes) 906mm System Size/ Enclosure width APC Part No. Installed weight 10kVA 352mm SUVT10KHS 134kg 15kVA 352mm SUVT15KHS 134kg 20kVA 352mm SUVT20KHS 134kg 30kVA 523mm SUVT30KHS 182.5kg 40kVA 523mm SUVT40KHS 182.
Appendix – UPS Components and Options User interface ! Output Pwr Zone Probe 10/100Base-T Reset 10/100 AP9619 Network Management Card EM Display: user-control interface used to configure the functionality, monitor the system, set alarm thresholds, and provide audible and visual alarms. Network Management Card with Environmental Monitor (AP9619): used for remote system control and monitoring, e-mail notifications, etc.
Appendix – UPS Components and Options APC Network Management Card AP9619 (installed in UPS) and APC Humidity Sensor (Optional) Humidity Sensor ! Output Pwr Zone Probe 10/100Base-T Reset 10/100 AP9619 Network Management Card EM APC Smart-UPS VT Battery Temperature Sensor (Optional) 1 delivered with UPS Part no.
Appendix – UPS Components and Options Floor anchoring (Optional) ! Output Pwr Zone Probe 10/100Base-T Reset 10/100 AP9619 Network Management Card EM Reuse transport brackets as Floor Anchoring Brackets Floor-anchoring bolts are not provided with the UPS. Purchase the floor anchors locally.
Options Maintenance Bypass Panels Further details on APC Maintenance Bypass Panel (MBP) are available at www.apc.com. Note MBP for SUVT 10-20kVA MBP for SUVT 30-40kVA 305mm 450mm 305mm 126mm 400mm 126mm Part no. APC MBP for SUVT 10-20kVA SBPSU10K20HC1M1-WP Part no. APC MBP for SUVT 30-40kVA SBPSU30K40HC1M1-WP The Maintenance Bypass Panel provides overcurrent protection to the entire UPS system. It is also used to bypass the mains power around the UPS instead of through the system, e.g.
Appendix – Options APC Smart-UPS VT 10-40kVA Battery Breaker Box Front panel 360mm 270mm 183mm including front panel Part no. APC Smart-UPS VT 10-40kVA 400V Battery Breaker Box SUVTBB10K40H Customized Battery solutions Customized battery solutions are available from our Custom Engineering Group. Contact CEG through APC's Customer Support (contact numbers available on rear cover).
APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: • Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests. – www.apc.com (Corporate Headquarters) Connect to localized APC Web sites for specific countries, each of which provides customer support information. – www.apc.com/support/ Global support searching APC Knowledge Base and using e-support.