Automatic Floor Pressurization Sensor for Uniflair CW — Installation10
Evaporating fan regulation
Setpoint: the reference pressure value that needs to be
maintained by the modulation of the fans
Dead Band:
dead band regulation
Regul. Band:
proportional regulation band
Integral Time:
integral time
Derivat. Time:
derivative time
Air pressure:
the reading taken by the sensor
Evaporating Fan:
evaporating fan regulation percentage
Alarm parameters
Alarm Level: low air pressure alarm activation level
Alarm Delay:
low air pressure alarm activation delay
time.
EVAPORATING FAN REGUL.
Setpoint Pa 020.0
Dead Band Pa 000.0
Regul. Band Pa 160.0
Integral Time s 040
Derivat.Time s 000
Air Pressure Pa 020.0
Evaporating Fan % 000
EVAPORATING FAN REGUL.
Alarm Level Pa 015.0
Alarm Delay s 060