Automatic Floor Pressurization Sensor for Uniflair CW — Installation 11
Configuration Settings with Units in a LAN
To configure fan speed modulation for several units connected through in a LAN, complete the following
steps:
1. From the main screen press the Prg key, select Settings Menu and press Enter to confirm.
2. Insert the Password Settings (see the envelope attached to the manual) and press Enter to
confirm.
3. Select LAN Settings and press Enter to confirm.
4. Scroll through the screens by pressing the Down key until the Parameters Setting screen appears.
5. After setting the parameters, press the Escape key several times until the main screen appears.
6. To save the data that has been entered, turn off the unit for several seconds, and then turn it back
on again.
7. Repeat steps 1–6 for each unit.
Note: Fan speed modulation settings can be determined through sensor reading of the unit, or
by calculating the average reading of all units in the LAN.
Air pressure control
Air Pressure Control:
Local Values:
Fan speed modulation is controlled by the
pressure reading taken by the sensor on each unit.
Mean Values:
Fan speed modulation is controlled by the
average pressure reading taken by the sensors on the
units connected in a local network.
LAN SETTINGS
Temp./Hum. Control
Mode: Local Values
Air Pressure Control
Mode: Local Values
LAN SETTINGS
Temp./Hum.Control
Mode: Local Values
Air Pressure Control
Mode: Mean Values