Installation manual

35Uniflair LE Accessories Manual
3. Connect the pump high float switch that leads to Digital Input 2 on the Uniflair unit (in series with leak
detection if applicable). A high water level condition in the pump reservoir causes a “Flood Alarm” on the
Uniflair unit. This alarm can be manually set to shutdown the unit if selected as a second level alarm.
4. If removed, replace the electrical component cover.
5. Apply power to the unit. The pump activates when the reservoir fills to the switch activation level.
Configuration
Using the LED display
1. Turn on power to the unit and wait for the main screen to appear on the display.
2. Press Prg.
3. Select SERVICE MENU, then press ENTER.
NOTE: The password is found inside the envelope attached to the manual. If the password has been
changed, enter the new password.
4. Press ENTER.
5. Select HARDWARE SETTINGS and press ENTER.
6. Navigate to “DIGITAL INPUT 2 CONFIGURATION”.
7. Check to ensure the existing setting is not used.
8. Press ENTER until the cursor stops under NOT USED.
9. Press UP or DOWN until “FLOODING SENSOR” appears on the display.
10.Press ENTER.
11. To exit, press the ESC key and navigate to the main screen.
SAS
RED 20
RED 0
RED 720
RED 51
JUMPER
UPC5+m
ID2
730
730
P
720
720
JUMPER JUMPER
720
51
SAS
JUMPER
51
20
20
5 6 7 8
SAS
RED 20
RED 0
RED 720
RED 51
JUMPER
UPC5+m
ID2
730
730
P
720
720
JUMPER
JUMPER
51
20
20
JUMPER
SAS
RED 20
RED 0
RED 720
RED 51
JUMPER
UPC5+m
ID2
730
JUMPER
51
20
20
JUMPER
JUMPER
730
720
na4815a
CONDENSATE DRAIN
PUMP ALARM CONTACT
FLOODING DETECTORS +
CONDENSATE DRAIN PUMP
STANDARD FACTORY
INSTALLATION
TERMINAL
BLOCKS
720 AND
730
TERMINAL
BLOCKS
720 AND
730