Installation manual
67Uniflair LE Accessories Manual
Transducer
Range Begin: The starting value of the transducer.
Range End: Ending value of the transducer.
Read Value: The reading taken by the sensor.
Delta: Maximum variation without activating the filter.
Time: Duration of the filter.
Value: Reading taken by the sensor.
Evaporating fan speed
Minimum speed: Minimum evaporating fan speed during modulation.
Maximum speed: Maximum evaporating fan speed during modulation.
Evaporating fan regulation
Setpoint: The reference pressure value that needs to be maintained by the
modulation of the fans.
Dead Band: Dead band regulation
Regul. Band: Proportional regulation band
Integral Time: integral time
Derivat. Time: derivative time
Air pressure: the reading taken by the sensor
Evaporating Fan: evaporating fan regulation percentage
Alarm parameters
Alarm Level: Low air pressure alarm activation level.
Alarm Delay: Low air pressure alarm activation delay time.
AIR PRESS. TRANSDUCER
Range Begin. Pa 000.0
Range End. Pa 100.0
Read Value Pa 020.0
INPUT FILTER
Delta Pa 4.0
Time s 01
Value Pa 020.0
EVAPORATING FAN REGULAT.
Minimum Speed : % 40
Maximum Speed: % 100
EVAPORATING FAN REGUL.
Setpoint Pa 020.0
Dead Band Pa 000.0
Regul. Band Pa 160.0
Integral Time s 040
Derivat. Time s 000
Air Pressure Pa 020.0
Evaporating Fan % 000