Installation manual

Uniflair LE Accessories Manual68
6. To exit, press the ESC key and navigate to the main screen.
Using the touchscreen
Path: Main > Configuration > Unit > Airflow > Group
1. Turn on the power to the unit and wait for the touchscreen to display.
NOTE: Settings may appear on a different screen.
2. Press Fan: Controlled by AFPS
3. Press Yes to enter your credentials.
4. Enter your credentials and begin configuration.
Fan: Controlled by AFPS: Present
Fan AFPS on Unit: Present
AFPS Setpoint: 20
AFPS Low Air Pressure Threshold: 15
AFPS Max. Fan Speed: 100%
AFPS Min. Fan Speed CW: 40%
Fan AFPS Control Type: Advanced
AFPS Deadband:100%
AFPS Regulation Band: 160
Air Pressure Transducer Input Filter Time: 1
AFPS Sensor Min: 0
AFPS Sensor Max: 100
AFPS Sensor Input Filter Value: 0
AFPS Sensor Input Filter Delta Threshold: 4
AFPS Integral Time: 40
AFPS Derivative Time: 0
Fan Speed Derivative Time (using AFPS): 0
Fan Speed Integral Time using AFPS: 40
5. Press the Home button to return to the main screen.
Configuring the LAN settings using the LED display
1. From the main screen press the Prg key, select Settings Menu and press Enter to confirm.
NOTE: The password is found inside the envelope attached to the manual. If the password has been
changed, enter the new password instead
2. Enter the password.
3. Select LAN Settings and press Enter to confirm.
4. Navigate to the Parameters Setting screen. The following provides settings for air pressure control.
EVAPORATING FAN REGUL.
Alarm Level Pa 015.0
Alarm Delay s 060